T4V 250 TMA 160-1600 3p F F

Produttore:
ABB
Abb

Ac86cced424be0a90cdaf18bb95fe701477625aa medium
Codice Nuova Elva
1SDA054249R1
Codice produttore
1SDA054249R1
Disponibilità
Invia RdO

C.BREAKER TMAX T4V 250 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 160 I3=800...1600 A

Specifications

Ordering

EAN8015644553463
Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width105 mm
Product Net Height205 mm
Product Net Depth / Length103.5 mm
Product Net Weight2.35 kg

Container Information

Package Level 1 Depth / Length285 mm
Package Level 1 Gross Weight2.5 kg
Package Level 1 EAN8015644553463
Package Level 1 Units1 piece
Package Level 1 Width248 mm
Package Level 1 Height240 mm

Additional Information

Electrical Durability8000 cycle120 cycles per hour
Mechanical Durability20000 cycle240 cycles per hour
Number of Poles3
Power Lossat Rated Operating Conditions per Pole 7,4 W
Product Main TypeSACE Tmax T
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)Main Circuit 160 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 200 kA(400 V AC) 200 kA(415 V AC) 200 kA(440 V AC) 180 kA(500 V AC) 150 kA(690 V) 150 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 200 kA(400 V AC) 200 kA(415 V AC) 200 kA(440 V AC) 180 kA(500 V AC) 150 kA(690 V AC) 150 kA(250 V DC) 2 Poles in Series 100 kA(500 V DC) 2 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)250 A
Release TypeTM
StandardsIEC 60947
Sub-typeT4
Suitable ForT4
Suitable for Product ClassMoulded Case Circuit Breakers
Terminal Connection TypeFixed Circuit-BreakersFront
Test Voltage Max (Utest)3500 V
Test Voltage at Industrial Frequency for 1 Minute3500 V
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 7EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
UNSPSC39121100
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)