T6L 630 PR222DS/P-LSI In=630 4p F F

Produttore:
ABB
Abb

Ea5f9c52ba883453c6646a49dce0f8499bd929ff medium
Prezzo (IVA esclusa)
€ 5892.30
Codice Nuova Elva
1SDA060264R1
Codice produttore
1SDA060264R1
Disponibilità
Tempo di consegna standard: 5 giorni

C.BREAKER TMAX T6L 630 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR222DS/P-LSI R 630

Specifications

Ordering

E-Number (Finland)3655456
Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width280 mm
Product Net Height268 mm
Product Net Depth / Length103.5 mm
Product Net Weight12 kg

Container Information

Package Level 1 Depth / Length370 mm
Package Level 1 Gross Weight14 kg
Package Level 1 EAN8015644627263
Package Level 1 Units1 piece
Package Level 1 Width305 mm
Package Level 1 Height285 mm

Additional Information

Electrical Durability7000 cycle60 cycles per hour
Mechanical Durability20000 cycle120 cycles per hour
Number of Poles4
Power Lossat Rated Operating Conditions per Pole 20 W
Product Main TypeSACE Tmax T
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)Main Circuit 630 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 150 kA(230 V AC) 150 kA(380 V AC) 75 kA(400 V AC) 75 kA(415 V AC) 75 kA(440 V AC) 60 kA(500 V AC) 49 kA(690 V AC) 22.5 kA
Rated Short-time Withstand Current (Icw)for 1 s 7.6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 80 kA(500 V AC) 65 kA(690 V AC) 30 kA
Rated Uninterrupted Current (Iu)630 A
ReleasePR222DS/P-LSI
Release TypeEL
Short-Circuit Performance LevelL
StandardsIEC
Sub-typeT6
Suitable ForT6
Suitable for Product ClassMoulded Case Circuit Breakers
Terminal Connection TypeFixed Circuit-BreakersFront
Test Voltage Max (Utest)3500 V
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)