T7L 1250 PR331/P LSIG In=1250A 3p F F
- Produttore:
- ABB
- Prezzo (IVA esclusa)
- € 6741.90
- Codice Nuova Elva
- 1SDA062932R1
- Codice produttore
- 1SDA062932R1
- Disponibilità
- Tempo di consegna standard: 5 giorni
C.BREAKER TMAX T7L 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 1250
Specifications
Ordering | |
---|---|
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362090 |
Dimensions | |
Product Net Width | 210 mm |
Product Net Height | 268 mm |
Product Net Depth / Length | 154 mm |
Product Net Weight | 9.7 kg |
Container Information | |
Package Level 1 Gross Weight | 11.2 kg |
Package Level 1 EAN | 8015644654818 |
Package Level 1 Units | 1 piece |
Package Level 1 Width | 280 mm |
Package Level 1 Height | 350 mm |
Package Level 1 Depth / Length | 360 mm |
Additional Information | |
Electrical Durability | 2000 cycle60 cycles per hour |
Mechanical Durability | 10000 cycle60 cycles per hour |
Number of Poles | 3 |
Power Loss | at Rated Operating Conditions per Pole 47 W |
Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker |
Product Type | CB |
Rated Current (In) | Main Circuit 1250 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 120 kA(400 V AC) 120 kA(415 V AC) 120 kA(440 V AC) 100 kA(500 V AC) 64 kA(690 V AC) 37.5 kA |
Rated Short-time Withstand Current (Icw) | for 1 s 20 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 120 kA(400 V AC) 120 kA(415 V AC) 120 kA(440 V AC) 100 kA(500 V AC) 85 kA(690 V AC) 50 kA |
Rated Uninterrupted Current (Iu) | 1250 A |
Release | PR331/P LSIG |
Release Type | EL |
Short-Circuit Performance Level | L |
Standards | IEC |
Sub-type | T7 |
Suitable For | T7 |
Suitable for Product Class | Moulded Case Circuit Breakers |
Terminal Connection Type | Fixed Circuit-BreakersFront |
Version | F |
Classifications | |
ETIM 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |