E2.2B 1600 Ekip Dip LSI 4p F HR
- Produttore:
- ABB
- Prezzo (IVA esclusa)
- € 9793.80
- Codice Nuova Elva
- 1SDA071612R1
- Codice produttore
- 1SDA071612R1
- Disponibilità
- Invia RdO
C.BREAKER SACE EMAX2 E2.2B 1600 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LSI R 1600 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Specifications
Ordering | |
---|---|
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362090 |
Dimensions | |
Product Net Width | 366 mm |
Product Net Height | 371 mm |
Product Net Depth / Length | 270 mm |
Product Net Weight | 53 kg |
Container Information | |
Package Level 1 Gross Weight | 58 kg |
Package Level 1 EAN | 8015644754624 |
Package Level 1 Units | 1 piece |
Package Level 1 Width | 515 mm |
Package Level 1 Height | 610 mm |
Package Level 1 Depth / Length | 615 mm |
Environmental | |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Additional Information | |
Current Type | AC |
Electrical Durability | Ue =< 440 V 12000 cycleUe = 500 ... 690 V 10000 cycle30 cycles per hour |
Mechanical Durability | 25000 cycle60 cycles per hour |
Neutral Pole Current ([%Iu]) | 100 % |
Number of Poles | 4 |
Power Loss | 136 W |
Product Main Type | SACE Emax 2 |
Product Name | Air Circuit Breaker |
Product Type | Air Circuit Breaker |
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
Rated Current (In) | 1600 A |
Rated Voltage (Ur) | 690 V |
Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
Rated Insulation Voltage (Ui) | AC 1000 V |
Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA(230 V AC) 42 kA(380 V AC) 42 kA(400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA |
Rated Short-time Withstand Current (Icw) | for 1 s 42 kAfor 3 s 42 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA(500 V AC) 42 kA(525 V AC) 42 kA(690 V AC) 42 kA |
Rated Uninterrupted Current (Iu) | 1600 A |
Release | Ekip Dip LSI |
Release Type | EL |
Short-Circuit Performance Level | B |
Standards | IEC |
Sub-type | E2.2 |
Terminal Connection Type | Rear flat Horizontal |
Version | F |
Classifications | |
ETIM 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |