CT-ERS.22S Time relay, ON-delay 2c/o, 24-48VDC, 24-240VAC
- Produttore:
- ABB
The CT-ERS.22S is a single-function electronic time relay from the CT-S timer range. It provides an ON-delay (delay on make) function with 10 time ranges from 0.05 s to 300 h. This time relay operates with a rated control supply voltage of 24 - 48 V DC / 24 - 240 V AC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
Specifications
Ordering | |
---|---|
EAN | 4016779851466 |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85364900 |
Container Information | |
Package Level 1 Units | 1 piece |
Package Level 1 Width | 97 mm |
Package Level 1 Depth / Length | 30 mm |
Package Level 1 Height | 109 mm |
Package Level 1 Gross Weight | 0.144 kg |
Package Level 1 EAN | 4016779851466 |
Dimensions | |
Product Net Height | 85.6 mm |
Product Net Depth / Length | 103.7 mm |
Product Net Weight | 0.121 kg |
Product Net Width | 22.5 mm |
Technical | |
Timer Relay Type | ON-Delay |
Time Range | 0.05 s ... 300 h |
Rated Control Supply Voltage (Us) | 24 ... 240 V AC24 ... 48 V DC |
Rated Frequency (f) | 50 Hz60 HzDC |
Output | 2 c/o (SPDT) contacts |
Terminal Type | Screw Terminals |
Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
Rated Operational Current AC-15 (Ie) | (230 V) 3 A |
Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
Rated Operational Current DC-13 (Ie) | (24 V) 2 A |
Minimum Switching Capacity | 12 V10 mA |
Rated Impulse Withstand Voltage (Uimp) | Input Circuit 4 kVOutput Circuit 1 / Output Circuit 2 4 kV |
Rated Insulation Voltage (Ui) | Input Circuit / Output Circuit 500 VOutput Circuit 1 / Output Circuit 2 300 V |
Degree of Protection | Housing IP50Terminals IP20 |
Overvoltage Category | III |
Pollution Degree | 3 |
Short-Circuit Protective Devices | Output Circuit NC - F Type Fuses 6 AOutput Circuit NO - F Type Fuses 10 A |
Electrical Durability | AC-12 100000 cycle |
Mechanical Durability | 30000000 cycle |
Connecting Capacity | Flexible with Ferrule 1x 0.5 ... 2.5 mm²Flexible with Ferrule 2x 0.5 ... 1.5 mm²Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²Flexible 1x 0.5 ... 2.5 mm²Flexible 2x 0.5 ... 1.5 mm²Rigid 1x 0.5 ... 4 mm²Rigid 2x 0.5 ... 2.5 mm² |
Tightening Torque | 0.6 ... 0.8 N·m |
Wire Stripping Length | 8 mm |
Mounting Position | Any |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Standards | CAN/CSA C22.2 No.14EN 50581IEC/EN 61812-1UL 508 |
Environmental | |
Ambient Air Temperature | Operation -25 ... +60 °CStorage -40 ... +85 °C |
RoHS Status | Following EU Directive 2011/65/EU |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA | Output Circuit 300 V AC |
Contact Rating UL/CSA | B300 |
Connecting Capacity UL/CSA | Flexible 1x 18-14 AWGFlexible 2x 18-16 AWGRigid 1x 20-12 AWGRigid 2x 20-14 AWG |
Tightening Torque UL/CSA | 7.08 in·lb |
Classifications | |
Object Classification Code | K |
ETIM 4 | EC001439 - Timer relay |
ETIM 5 | EC001439 - Timer relay |
ETIM 6 | EC001439 - Timer relay |
ETIM 7 | EC001439 - Timer relay |
eClass | 7.0 27371790 |
UNSPSC | 39121519 |
E-Number (Sweden) | 4033116 |