MS132-16T Circuit Breaker for Primary Transformer Protection

Produttore:
ABB
Abb

E8c5fbdcfbef389260b83d2f33cb3815f2f844d4 medium
Codice Nuova Elva
MS13216T
Codice produttore
1SAM340000R1011
Disponibilità
Invia RdO

The circuit breaker for transformer protection MS132-16T is a compact 45 mm width device designed to protect control transformers on the primary side. This device has a rated operational current of Ie = 16 A. It allows fuse-less protection against overload and short-circuit. The short-circuit current setting is fixed to 20 times the rated operational current to handle the high inrush current generated by transformers. The device allows manually connect and disconnect the transformer from the mains thanks of its built-in disconnection function. The circuit breaker for transformer protection offers a rated service short-circuit breaking capacity of Ics = 100 kA at 400 VAC and a trip class 10. Further features are temperature compensation, trip-free mechanism, rotary handle with a clear switch position indication and short circuit trip indicator. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, power in-feed blocks and terminal spacers are available as accessory.

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85362010

Dimensions

Product Net Width45 mm
Product Net Height97.8 mm
Product Net Depth / Length86.05 mm
Product Net Weight0.31 kg

Technical

Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (Ie)16 A
Rated Frequency (f)Main Circuit 50 HzMain Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Rated Insulation Voltage (Ui)690 V
Power Lossat Rated Operating Conditions per Pole 0.9 W
Number of Poles3
Conventional Free-air Thermal Current (Ith)Main Circuit 16 A
Degree of ProtectionHousing IP20Main Circuit Terminals IP10
Pollution Degree3
Electrical Durability50000 cycle
Mechanical Durability100000 cycle
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 6 mm²Flexible 1/2x 1 ... 2.5 mm²Flexible 1/2x 2.5 ... 6 mm²Rigid 1/2x 1 ... 2.5 mm²Rigid 1/2x 2.5 ... 6 mm²
Tightening TorqueMain Circuit 2 N·m
Wire Stripping LengthMain Circuit 10 mm
Recommended Screw DriverM4Pozidriv 2
Mounting PositionPosition 1 to 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 9 mmOther Device Same Type, Vertical 150 mm
Actuator TypeRotary Handle
Contact Position IndicationON / OFF / TRIP
StandardsIEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 100 kA(400 V AC) 100 kA(440 V AC) 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)320 A
Setting Range10 ... 16 A

Technical UL/CSA

Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Ampere Rating UL/CSA16 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 1 Hp(220 ... 240 V AC) Single Phase 2 Hp
Full Load Amps Motor Use(120 V AC) Single Phase 16 A(220 ... 240 V AC) Single Phase 12 A
Locked Rotor Amps(120 V AC) Single Phase 96 A(220 ... 240 V AC) Single Phase 96 A
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 16-8 AWGStranded 1/2x 16-8 AWG
Tightening Torque UL/CSAMain Circuit 16 in·lb

Environmental

Ambient Air TemperatureAround the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations acc. to IEC 60068-2-65g / 3 ... 150 Hz
RoHS StatusFollowing EU Directive 2011/65/EU

Container Information

Package Level 1 Units1 piece
Package Level 1 Width92 mm
Package Level 1 Depth / Length102 mm
Package Level 1 Height50 mm
Package Level 1 Gross Weight0.325 kg
Package Level 1 EAN4013614485022
Package Level 2 Units40 piece
Package Level 2 Width280 mm
Package Level 2 Depth / Length395 mm
Package Level 2 Height210 mm
Package Level 2 Gross Weight13.386 kg
Package Level 2 EAN4013614487224

Classifications

Object Classification CodeF
ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
eClassV11.0 : 27370409
IDEA Granular Category Code (IGCC)4813 >> Circuit breakers
E-Number (Finland)3707273

Documentazione