S804N-D40 High Performance MCB
- Produttore:
- ABB
- Codice Nuova Elva
- S120518
- Codice produttore
- 2CCS894001R0401
- Disponibilità
- Tempo di consegna standard: 24 giorni
The S804N-D40 is a 4-pole High Performance Circuit breaker with D-Characteristic, with cage terminal and a rated current of 40 A. It is a current limiting device with a maximum breaking capacity of 36kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S804N-D40 complies with IEC/EN 60898-1 and IEC/EN 60947-2 and allows the use for residential, commercial and industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S804N-D40 more comfortable. Due to the fast arc extinction of S804N-D40 your application will be secured.
Specifications
Technical | |
---|---|
Standards | IEC/EN 60947-2IEC/EN 60898-1 |
Number of Poles | 4 |
Rated Frequency (f) | 50...60 Hz |
Rated Short-Circuit Capacity (Icn) | (400 V) 25 kA(230 V) 25 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 / 415 V AC) 36 kA(254 / 440 V AC) 20 kA(400 / 690 V AC) 4.5 kA(500 V DC) 20 kA(230 V) 36 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (240 / 415 V AC) 30 kA(254 / 440 V AC) 15 kA(400 / 690 V AC) 3 kA(125 V DC) 20 kA |
Energy Limiting Class | 3 |
Overvoltage Category | IV |
Pollution Degree | 3 |
Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Housing Material | Insulation group I, RAL 7035 |
Actuator Marking | I / O |
Number of Protected Poles | 4 |
Contact Position Indication | ON / OFF / TRIP |
Degree of Protection | IP20 |
Remarks | Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw |
Electrical Endurance | 6000 cycle |
Mechanical Endurance (Nendu) | 4000 cycle |
Terminal Type | Screw Terminals |
Connecting Capacity | Rigid 0 ... 50 mm²Flexible 0 ... 70 mm² |
Tightening Torque | 3.5 N·m31 in·lb |
Recommended Screw Driver | Pozidriv 2 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Tripping Characteristic | D |
Mounting Position | Any |
Built-In Depth (t2) | 82.5 mm |
Rated Current (In) | 40 A |
Rated Operational Voltage | 400/690 V AC375 V DCacc. to IEC 60898-1 690 V |
Rated Voltage (Ur) | 230 / 400 V |
Power Loss | 14.8 Wat Rated Operating Conditions per Pole 3.7 W |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 690 V |
Operational Voltage | Maximum 230/400 V ACMinimum 12 V AC |
Environmental | |
Ambient Air Temperature | Operation -25...60 °C |
Reference Ambient Air Temperature | acc. to IEC60947-2 30 °Cacc. to EN60898-1 30 °C |
Resistance to Shock acc. to IEC 60068-2-27 | 5 g30 ms |
Resistance to Vibrations acc. to IEC 60068-2-6 | 2 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie |
Environmental Conditions | Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycleDamp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96%Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100%Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °CDry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C |
RoHS Status | Following EU Directive 2011/65/EU |
Dimensions | |
Product Net Width | 106 mm |
Product Net Depth / Length | 82.5 mm |
Product Net Height | 95 mm |
Product Net Weight | 980 g |
Container Information | |
Package Level 1 Units | box 1 piece |
Package Level 1 Width | 105 mm |
Package Level 1 Depth / Length | 111 mm |
Package Level 1 Height | 99 mm |
Package Level 1 Gross Weight | 1010 g |
Package Level 1 EAN | 7612271205188 |
Ordering | |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362010 |
Classifications | |
Object Classification Code | F |
ETIM 8 | EC000042 - Miniature circuit breaker (MCB) |