S804N-D80 High Performance MCB
- Produttore:
- ABB
- Codice Nuova Elva
- S120521
- Codice produttore
- 2CCS894001R0801
- Disponibilità
- Tempo di consegna standard: 24 giorni
The S804N-D80 is a 4-pole High Performance Circuit breaker with D-Characteristic, with cage terminal and a rated current of 80 A. It is a current limiting device with a maximum breaking capacity of 36kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S804N-D80 complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S804N-D80 more comfortable. Due to the fast arc extinction of S804N-D80 your application will be secured.
Specifications
Technical | |
---|---|
Standards | IEC/EN 60947-2IEC/EN 60898-1 |
Number of Poles | 4 |
Rated Frequency (f) | 50...60 Hz |
Rated Short-Circuit Capacity (Icn) | (400 V) 25 kA(230 V) 25 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 / 415 V AC) 36 kA(254 / 440 V AC) 20 kA(400 / 690 V AC) 4.5 kA(500 V DC) 20 kA(230 V) 36 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (240 / 415 V AC) 30 kA(254 / 440 V AC) 15 kA(400 / 690 V AC) 3 kA(125 V DC) 20 kA |
Energy Limiting Class | 3 |
Overvoltage Category | IV |
Pollution Degree | 3 |
Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Housing Material | Insulation group I, RAL 7035 |
Actuator Marking | I / O |
Number of Protected Poles | 4 |
Contact Position Indication | ON / OFF / TRIP |
Degree of Protection | IP20 |
Remarks | Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw |
Electrical Endurance | 6000 cycle |
Mechanical Endurance (Nendu) | 4000 cycle |
Terminal Type | Screw Terminals |
Connecting Capacity | Rigid 0 ... 50 mm²Flexible 0 ... 70 mm² |
Tightening Torque | 3.5 N·m31 in·lb |
Recommended Screw Driver | Pozidriv 2 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Tripping Characteristic | D |
Mounting Position | Any |
Built-In Depth (t2) | 82.5 mm |
Rated Current (In) | 80 A |
Rated Operational Voltage | 400/690 V AC375 V DCacc. to IEC 60898-1 690 V |
Rated Voltage (Ur) | 230 / 400 V |
Power Loss | 25.6 Wat Rated Operating Conditions per Pole 6.4 W |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 690 V |
Operational Voltage | Maximum 230/400 V ACMinimum 12 V AC |
Environmental | |
Ambient Air Temperature | Operation -25...60 °C |
Reference Ambient Air Temperature | acc. to IEC60947-2 30 °Cacc. to EN60898-1 30 °C |
Resistance to Shock acc. to IEC 60068-2-27 | 5 g30 ms |
Resistance to Vibrations acc. to IEC 60068-2-6 | 2 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie |
Environmental Conditions | Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycleDamp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96%Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100%Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °CDry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C |
RoHS Status | Following EU Directive 2011/65/EU |
Dimensions | |
Product Net Width | 106 mm |
Product Net Depth / Length | 82.5 mm |
Product Net Height | 95 mm |
Product Net Weight | 980 g |
Container Information | |
Package Level 1 Units | box 1 piece |
Package Level 1 Width | 105 mm |
Package Level 1 Depth / Length | 111 mm |
Package Level 1 Height | 99 mm |
Package Level 1 Gross Weight | 1010 g |
Package Level 1 EAN | 7612271205218 |
Ordering | |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362090 |
Classifications | |
Object Classification Code | F |
ETIM 8 | EC000042 - Miniature circuit breaker (MCB) |