S803S-K6 High Performance MCB

Produttore:
ABB
Abb

F11dc6e32ed3c0effbc6b1f87937537ae5f46fbd medium
Codice Nuova Elva
S140824
Codice produttore
2CCS863001R0067
Disponibilità
Invia RdO

The S803S-K6 is a 3-pole High Performance Circuit breaker with K-Characteristic, with cage terminal and a rated current of 6 A. It is a current limiting device with a maximum breaking capacity of 50kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S803S-K6 complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S803S-K6 more comfortable. Due to the fast arc extinction of S803S-K6 your application will be secured.

Specifications

Technical

StandardsIEC/EN 60947-2UL 1077
Number of Poles3
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(240 / 415 V AC) 50 kA(254 / 440 V AC) 30 kA(400 / 690 V AC) 6 kA(125 V DC) 30 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(240 / 415 V AC) 40 kA(254 / 440 V AC) 22.5 kA(400 / 690 V AC) 4 kA(125 V DC) 30 kA
Energy Limiting Class3
Overvoltage CategoryIV
Pollution Degree3
Rated Impulse Withstand Voltage (Uimp)8 kV
Housing MaterialInsulation group I, RAL 7035
Actuator MarkingI / O
Contact Position IndicationON / OFF / TRIP
Degree of ProtectionIP20
Number of Protected Poles3
RemarksConnection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw
Electrical Endurance10000 cycle
Mechanical Endurance (Nendu)10000 cycle
Terminal TypeScrew Terminals
Connecting CapacityRigid 0 ... 50 mm²Flexible 0 ... 70 mm²
Tightening Torque3.5 N·m31 in·lb
Recommended Screw DriverPozidriv 2
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting PositionAny
Built-In Depth (t2)88.5 mm
Tripping CharacteristicK
Rated Current (In)6 A
Rated Operational Voltage400/690 V AC375 V DC
Power Lossat Rated Operating Conditions per Pole 1.7 W
Rated Insulation Voltage (Ui)690 V AC
Rated Frequency (f)50...60 Hz
Rated Short-Circuit Capacity (Icn)(400 V) 25 kA(230 V) 25 kA

Environmental

Ambient Air TemperatureOperation -25...60 °C
Reference Ambient Air Temperatureacc. to IEC60947-2 40 °Cacc. to EN60898-1 40 °C
Resistance to Vibrations acc. to IEC 60068-2-62 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie
Environmental ConditionsDamp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycleDamp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96%Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100%Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °CDry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C
RoHS StatusFollowing EU Directive 2011/65/EU

Technical UL/CSA

Interrupting Rating acc. to UL1077(480Y / 277 V AC) 14 kA(600Y / 347 V AC) 6 kA

Dimensions

Product Net Width81 mm
Product Net Depth / Length82.5 mm
Product Net Height95 mm
Product Net Weight735 g

Container Information

Package Level 1 Units1 piece
Package Level 1 Width105 mm
Package Level 1 Depth / Length86 mm
Package Level 1 Height99 mm
Package Level 1 Gross Weight770 g
Package Level 1 EAN7612271408244

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85362020

Classifications

Object Classification CodeF
ETIM 6EC000042 - Miniature circuit breaker (MCB)
ETIM 7EC000042 - Miniature circuit breaker (MCB)

Documentazione


Altri articoli da ABB

Richiedi un preventivo