Miniature Circuit Breaker - S200M - 2P - C - 32 A
- Produttore:
- ABB
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Specifications
Technical | |
---|---|
Standards | IEC/EN 60898-1IEC/EN 60947-2 |
Number of Poles | 2 |
Rated Frequency (f) | 50 / 60 Hz |
Rated Short-Circuit Capacity (Icn) | (230 V AC) 10 kA(400 V AC) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 25 kA(400 V AC) 15 kA(440 V AC) 15 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 7.5 kA |
Energy Limiting Class | 3 |
Overvoltage Category | III |
Pollution Degree | 3 |
Rated Impulse Withstand Voltage (Uimp) | 4 kVat 2000 m 5 kVat Sea Level 6.2 kV |
Dielectric Test Voltage | 50/60 Hz, 1 min: 2 kV |
Housing Material | Insulation Group II, RAL 7035 |
Number of Protected Poles | 2 |
Actuator Material | Insulation Group II, Black, Sealable |
Actuator Marking | I / O |
Contact Position Indication | Red ON / Green OFF |
Degree of Protection | IP20Enclosure with Cover IP40 |
Electrical Endurance | 10000 AC cycle |
Mechanical Endurance (Nendu) | 20000 cycle |
Terminal Type | Screw Terminals |
Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
Connecting Capacity | Busbar 10 / 10 mm²Flexible with Ferrule 0.75 ... 25 mm²Flexible 0.75 ... 25 mm²Rigid 0.75 ... 35 mm²Stranded 0.75 ... 35 mm² |
Tightening Torque | 2.8 N·m |
Tripping Characteristic | C |
Recommended Screw Driver | Pozidriv 2 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position | Any |
Built-In Depth (t2) | 69 mm |
Installation Size | acc. to DIN 43880 1 |
Power Supply Connection | Arbitrary |
Rated Current (In) | 32 A |
Rated Operational Voltage | acc. to IEC 60898-1 400 V ACacc. to IEC 60947-2 440 V AC |
Rated Voltage (Ur) | 400 V AC |
Power Loss | 7.4 Wat Rated Operating Conditions per Pole 3.7 W |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
Operational Voltage | Maximum (Incl. Tolerance) 125 V DCMaximum (Incl. Tolerance) 440 V ACMinimum 12 V ACMinimum 12 V DC |
Environmental | |
Ambient Air Temperature | Operation -25 ... +55 °CStorage -40 ... +70 °C |
Reference Ambient Air Temperature | 30 °C |
Resistance to Shock acc. to IEC 60068-2-27 | 25g / 2 shocks / 13 ms |
Resistance to Vibrations acc. to IEC 60068-2-6 | 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In |
Environmental Conditions | 28 cycleswith 55 °C / 90-96 %and 25 °C / 95-100 % |
RoHS Status | Following EU Directive 2011/65/EU |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA | 125 V DC480Y/277 V AC |
Connecting Capacity UL/CSA | Busbar 14-8 AWGConductor 14-4 AWG |
Tightening Torque UL/CSA | 18 in·lb |
Interrupting Rating acc. to UL1077 | (125 V DC) 10 kA(277 V AC) 6 kA(480Y / 277 V AC) 6 kA |
Dimensions | |
Product Net Width | 35 mm |
Product Net Depth / Length | 69 mm |
Product Net Height | 88 mm |
Product Net Weight | 0.25 kg |
Container Information | |
Package Level 1 Units | carton 5 piece |
Package Level 1 Width | 92 mm |
Package Level 1 Depth / Length | 183 mm |
Package Level 1 Height | 80 mm |
Package Level 1 Gross Weight | 1.3 kg |
Package Level 1 EAN | 4016779605755 |
Package Level 2 Units | carton 60 piece |
Package Level 2 Width | 275 mm |
Package Level 2 Depth / Length | 400 mm |
Package Level 2 Height | 210 mm |
Package Level 2 Gross Weight | 15.4 kg |
Package Level 2 EAN | 4016779977449 |
Ordering | |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362010 |
E-Number (Sweden) | 2101230 |
E-Number (Finland) | 3210801 |
Classifications | |
Object Classification Code | F |
ETIM 8 | EC000042 - Miniature circuit breaker (MCB) |
eClass | V11.0 : 27141901 |