XT1B 160 TMD 125-1250 3p F F
- Produttore:
- ABB
C.BREAKER TMAX XT1B 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 125-1250 A
Specifications
Ordering | |
---|---|
E-Number (Finland) | 3640496 |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362090 |
Dimensions | |
Product Net Width | 76.2 mm |
Product Net Height | 130 mm |
Product Net Depth / Length | 70 mm |
Product Net Weight | 1.08 kg |
Container Information | |
Package Level 1 Depth / Length | 143 mm |
Package Level 1 Gross Weight | 1.137 kg |
Package Level 1 EAN | 8015644007157 |
Package Level 1 Units | 1 piece |
Package Level 1 Width | 128 mm |
Package Level 1 Height | 135 mm |
Environmental | |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Additional Information | |
Circuit Breaker Type to be Associated | Power Distribution |
Current Type | AC/DC |
Electrical Durability | 120 cycles per hour8000 cycle |
Mechanical Durability | Nr. Operations 240 cycles per hourNr. Operations 25000 cycle |
Number of Poles | 3 |
Opening Time | CB with SOR 15 msCB with UVR 15 ms |
Order Multiple | 1 piece |
Power Loss | at Rated Operating Conditions per Pole 10.7 W |
Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker |
Product Type | CB |
Rated Current (In) | 125 A |
Rated Frequency (f) | 50 / 60 Hz |
Rated Voltage (Ur) | 690 V |
Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 1250 A |
Rated Insulation Voltage (Ui) | 800 V |
Rated Operational Voltage | 690 V AC500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 25 kA(230 V AC) 25 kA(240 V AC) 25 kA(380 V AC) 18 kA(415 V AC) 18 kA(440 V AC) 11.25 kA(500 V AC) 8 kA(525 V AC) 6 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 18 kA(500 V DC) 3 Poles in Series 18 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 25 kA(230 V AC) 25 kA(240 V AC) 25 kA(380 V AC) 18 kA(415 V AC) 18 kA(440 V AC) 15 kA(500 V AC) 8 kA(525 V AC) 6 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 18 kA(500 V DC) 3 Poles in Series 18 kA |
Rated Uninterrupted Current (Iu) | 160 A |
Release | TMD |
Release Type | TM |
Setting Range | 87.5...125 A |
Short-Circuit Performance Level | B |
Standards | IEC |
Sub-type | XT1 |
Terminal Connection Type | Fixed Circuit-Breakers |
Version | F |
Classifications | |
ETIM 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |