XT2H 160 TMA 50-500 3p F F

Produttore:
ABB
Abb

040fb66a7412233221190d177a0fa29b96f0ddd3 medium
Codice Nuova Elva
XT2H50TMA3
Codice produttore
1SDA067599R1
Disponibilità
Invia RdO

C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 50 I3=250...500 A

Specifications

Ordering

EAN8015644014957
Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width90 mm
Product Net Height130 mm
Product Net Depth / Length82.5 mm
Product Net Weight1.1 kg

Container Information

Package Level 1 Depth / Length145 mm
Package Level 1 Gross Weight1.66 kg
Package Level 1 EAN8015644014957
Package Level 1 Units1 piece
Package Level 1 Width130 mm
Package Level 1 Height208 mm

Additional Information

Circuit Breaker Type to be AssociatedPower Distribution
Current TypeAC/DC
Electrical Durability120 cycles per hour8000 cycle
Mechanical DurabilityNr. Operations 240 cycles per hourNr. Operations 25000 cycle
Number of Poles3
Opening TimeCB with SOR 15 msCB with UVR 15 ms
Order Multiple1 piece
Power Lossat Rated Operating Conditions per Pole 4.09 W
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)50 A
Rated Frequency (f)50 / 60 Hz
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)300…500 A
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA(250 V DC) 2 Poles in Series 70 kA(500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA(250 V DC) 2 Poles in Series 70 kA(500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)160 A
Release TypeTM
Setting Range35...50 A
StandardsIEC
Sub-typeXT2
Terminal Connection TypeFixed Circuit-Breakers
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 7EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
UNSPSC39120000
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)

Altri articoli da ABB