Fuse Amp-Trap 2000® 600V 4A Time-Delay Class J AJT Series

Produttore:
Mersen/Ferraz Shawmut
Mersen%20ferraz%20shawmut

67db5bc9f74b6c7f4b7d8e818c7b5c5f2763b1e4 medium
Codice Nuova Elva
AJT4
Codice produttore
AJT4
Disponibilità
Invia RdO

Amp-Trap 2000® AJT fuses provide non-indication as well as a SmartSpot visual open fuse indicator. With advanced material technology the AJT fuse provides IEC Type 2 No Damage protection to main, feeder, and branch circuits, for all types of loads — yet, they require only half the mounting space needed for 600VAC Class RK fuses. AJT’s time-delay characteristics are ideal for handling typical motor and transformer inrush currents, while also providing superior current-limiting ability.

Features

  • Non-indicating or solid state SmartSpot visual blown fuse indicator

  • Time-delay for motor starting and transformer inrush

  • 300kA interrupting rating - self-certified, UL witnessed tests

  • Extremely current-limiting for low peak let-thru current

  • Most current-limiting UL class fuse

  • Recommended for Arc Flash energy reduction

  • Small footprint requires less mounting space and allows smaller, more economical fuse blocks

  • Easy 2-to-1 selectivity for prevention of nuisance shutdowns

  • Unique Class J dimensions prevent replacement errors

  • High-visibility orange label gives instant brand recognition

  • Metal-embossed date and catalog number for traceability and lasting identification

  • Fiberglass body provides dimensional stability in harsh industrial settings

  • High-grade silica filler ensures fast arc quenching

  • Optional EI indicator/switch mount for AJT70 to 600 open fuse indication

  • Motor circuits

  • Mains

  • Feeders

  • Branch circuits

  • Lighting, heating & general loads

  • Transformers

  • Control panels

  • Circuit breaker back-up

  • Bus duct

  • Load centers

  • UL listed to standard 248-8 File E2137

  • DC listed to UL standard 248

  • CSA certified to standard C22.2 No. 248.8

  • IEC 60269-2-1

  • UL listed

  • DC tested to UL standard 248

  • Approvals & Standards

Specifications

Amperage4 A
Diameter2.0574 cm
Frequency50 Hz
Fuse ClassClass J
Insulation MaterialGMG
Length5.715 cm
Mounting TypeClip
Package Height4.2926 cm
Package Length10.795 cm
Package Weight0.95254 kg
Package Width6.0452 cm
Package Quantity10
Rated Voltage AC600 V
Rated Voltage DC500 V
Terminal MaterialTin-Plated Copper
Terminal TypeFerrule
Weight0.09072 kg

Specifications

Sell Pack Weight2.1 lb
Sell Pack Width2.38 in
Sell Pack Length4.25 in
Body/Insulating MaterialGMG
Connection/Terminal TypeFerrule
Sell Pack Quantity10 Each
Speed/CharacteristicTime Delay
Fuse ClassClass J
Connection/Terminal MaterialTin-Plated Copper
Frequency50/60 Hz
Sell Pack Height1.69 in
Rated voltage AC UL600 V
Rated voltage DC UL500 V
Product Weight0.2 lb
Product Diameter0.81 in
Product Length2.25 in
MountingClip
Ampere Rating4 A
AC Max I.R./Breaking Capacity: I1200 kA
ROHS CompliantYes

Documentazione


Altri articoli da Mersen/Ferraz Shawmut

Richiedi un preventivo