MULTIVERT 160A/100mm, 3-pole switching terminal: clamp straps, for ESM

Produttore:
Mersen/Ferraz Shawmut
Mersen ferraz shawmut

4ff38940fb79bc4031a3446ed4f2fbcdb584f70c medium
Prezzo (IVA esclusa)
€ 234.28
Codice Nuova Elva
C1023134
Codice produttore
C1023134
Disponibilità
Invia RdO

MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 160A triple pole switching are for installation on to 100 mm and 185 mm bus bar systems. MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00 160A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.

Features

  • Installation on to 100 and 185mm bus bar system

  • Symmetrical switch - top/bottom cable terminal connection

  • Touch protection IP 30 with central cover

  • Parking position of switch operating cover even with fuse-links inserted

  • Electronic fuse monitoring or indicator for switch door position - optional

  • Safe on load connection/disconnection in accordance with IEC 60947-3

  • IEC/EN 60 947-3

  • For NH-fuse links size 000/00 in accordance with IEC/EN 60 269-2, VDE 0636-2

Specifications

Country of OriginCzech Republic
Frequency50 Hz
Number of Poles3

Specifications

Varieties of cable terminationscrew, clamp strap, AlCu clamp, frame clamp, V-terminal
Rated Impulse Withstand Voltage8 kV
Rated Insulation Voltage1000 V
Rated Sc Withstand4.5 kA / 1 s
Rated Voltage Ac Iec690 V
Rated Short Circuit Making Capacity With Solid Links Icm4.5 kA
Country Of OriginCZ
Product LineMULTIVERT® 160A, Size 00, 690VAC, Triple Pole Switching
Product BrandMULTIVERT®
Fuse Size00
Installation MountingBus bar system 100 mm
Frequency Hz50 ... 60 Hz
Number Of Poles3-Pole
Utilization CategoryAC 23 B @ Ue = AC 400 V; Ie = 160 A
Utilization Category 2AC 22 B @ Ue = AC 500 V; Ie = 160 A
Utilization Category 3AC 22 B @ Ue = AC 690 V; Ie = 100 A
Switchability1 x triple pole
Short Circuit Current Rating Sccr80kA@Ue = AC 400 V; Ie = 160 A / 80kA@Ue = AC 500 V; Ie = 160 A / 50kA@Ue = AC 690 V; Ie = 100 A
Conventional Free Air Thermal Current - Solid Links250 A
Conventional Free Air Thermal Current With Fuse-Links Ith160 A
Max Power Dissipation Of Fuse Links Pn12 W
Max Power Dissipation Of Solid Links Pn1.2 W
Power Dissipation By Ith Without Fuse-Links18 W
Power Dissipation Without Solid Links44 W

Documentazione


Altri articoli da Mersen/Ferraz Shawmut

Richiedi un preventivo