Hybrid motor starter - ELR W3- 24DC/500AC- 9I - 2297057
- Produttore:
- PHOENIX CONTACT
4 in 1" three-phase semiconductor reversing contactor with 24 V DC input, 9 A output current, emergency stop function, and adjustable overload switching.
Features
22.5 mm wide
Safety level according to IEC 61508-1: SIL 3, ISO 13849: PL e
Reduction in wiring
Long service life
Space saving
3-phase loop bridges
Adjustable current for bimetal function
Low-wear switching
GL-SW
CCC
EAC
IECEE CB Scheme
GL
ATEX
UL Listed
cUL Listed
Specifications
Depth | 114 mm |
---|---|
Height | 107 mm |
Strip Length | 8 mm |
Width | 22.5 mm |
Insulation characteristics | |
Rated insulation voltage | 500 V |
Rated surge voltage | 6 kV |
Overvoltage category | III |
Degree of pollution | 2 |
Designation | Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit |
Insulation | Safe isolation (IEC 60947-1/EN 50178) at operating voltage ≤ 300 V AC |
Insulation | Basic isolation (IEC 60947-1) at operating voltage 300 - 500 V AC |
Insulation | Safe isolation (EN 50178) at operating voltage 300 - 500 V AC |
Designation | Isolation characteristics between the control input and control supply voltage to auxiliary circuit |
Insulation | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
Insulation | Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Width | 22.5 mm |
Height | 107 mm |
Depth | 114 mm |
UL data | |
SCCR | 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
SCCR | 5 kA (500 V AC (fuse: 20 A RK5 (standard fault))) |
FLA | 6.5 A (500 V AC) |
Group installation | 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded) |
Group installation | 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded) |
Category code | NLDX |
Connection data | |
Connection name | Control circuits |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² - 2.5 mm² |
Conductor cross section flexible | 0.2 mm² - 2.5 mm² |
Conductor cross section AWG | 24 - 14 |
Torque | 0.5 Nm - 0.6 Nm |
Torque | 5 lbf-in. - 7 lbf-in. |
Connection data 2 | |
Connection name | Load circuit |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² - 2.5 mm² |
Conductor cross section flexible | 0.2 mm² - 2.5 mm² |
Conductor cross section AWG | 24 - 14 |
Torque | 0.5 Nm - 0.6 Nm |
Torque | 5 lbf-in. - 7 lbf-in. |
Conformance/approvals | |
Designation | Category (ISO 13849) |
Designation | ATEX |
Identification | II (2) G [Ex e] [Ex d] [Ex px] |
Identification | II (2) D [Ex t] [Ex p] |
Certificate | PTB 07 ATEX 3145 |
Designation | UL approval |
Certificate | NLDX.E228652 |
Identification | ≤ 3 |
Designation | Safety Integrity Level (SIL, IEC 61508) |
Identification | 2 |
Additional text | Motor protection |
Designation | Performance Level (ISO 13849) |
Identification | ≤ e |
Additional text | Safe shutdown |
Input data | |
Input name | Control input right/left |
Rated actuating voltage UC | 24 V DC |
Triggering voltage range | 19.2 V DC - 30 V DC |
Rated actuating current IC | 5 mA |
Switching threshold | 9.6 V ('0' signal) |
Switching threshold | 19.2 V ('1' signal) |
Switching level | < 5 V DC (For EMERGENCY STOP) |
Typical response time | < 35 ms |
Typical turn-off time | < 40 ms |
Ambient conditions | |
Ambient temperature (operation) | -25 °C - 70 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C - 80 °C |
Maximum altitude | ≤ 2000 m |
Degree of protection | IP20 |
Output data reply output | |
Output name | Acknowledge output |
Note | Confirmation: floating change-over contact, signal contact |
Contact type | 1 PDT |
Switching capacity according to IEC 60947-5-1 | 3 A (230 V, AC15) |
Switching capacity according to IEC 60947-5-1 | 2 A (24 V, DC13) |
Output data load output | |
Output name | AC output |
Rated operating voltage Ue | 500 V AC |
Operating voltage range | 42 V AC - 550 V AC |
Rated operating current Ie | 9 A (AC-51) |
Rated operating current Ie | 6.5 A (AC-53a) |
Mains frequency | 50/60 Hz |
Load current range | 1.5 A - 9 A (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
Cooling time | 20 min. (for auto reset) |
Leakage current | 0 mA |
Residual voltage | < 0.5 V |
Surge current | 100 A (t = 10 ms) |
Type of protection | Surge protection |
Device supply | |
Rated control supply current IS | 40 mA |
Type of protection | Surge protection |
Type of protection | Reverse polarity protection |
Rated control circuit supply voltage US | 24 V DC |
Control supply voltage range | 19.2 V DC - 30 V DC |
Standards and Regulations | |
Designation | Standards/regulations |
Standards/regulations | DIN EN 50178 |
Standards/regulations | EN 60947 |
Standards/regulations | IEC 61508 |
Standards/regulations | ISO 13849 |