DC/DC converters - QUINT-PS/24DC/48DC/ 5 - 2320128

Produttore:
PHOENIX CONTACT
Phoenix contact

0900fde72308b5bd617b2225ec512f4ab4f6ff8b medium
Prezzo (IVA esclusa)
€ 479.06
Codice Nuova Elva
2320128
Codice produttore
2320128
Disponibilità
Invia RdO

Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 24 V DC, output: 48 V DC/5 A

Features

  • Reliable starting of difficult loads, thanks to the static POWER BOOST power reserve with up to 125% nominal current permanently

  • Preventive function monitoring indicates critical operating states before errors occur

  • Constant voltage: output voltage regenerated even at the end of long cables

  • Support conversion to various voltage levels

  • Electrical isolation: for setting up independent supply systems

  • BV

  • cULus Listed

  • EAC

  • cULus Recognized

  • LR

  • RINA

  • NK

  • IECEE CB Scheme

  • DNV GL

  • ABS

  • UL Listed

  • cUL Listed

  • UL Recognized

  • cUL Recognized

Specifications

Depth125 mm
Height130 mm
Output Voltage48 V
Strip Length7 mm
Voltage10 V
Width48 mm

Output data

Nominal output voltage48 V DC ±1 %
Setting range of the output voltage (USet)30 V DC - 56 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN)5 A (-25 °C - 60 °C)
POWER BOOST (IBoost)6.25 A (-25°C - 40°C permanent, UOUT = 48 V DC )
Selective Fuse Breaking (ISFB)30 A (12 ms)
Derating60 °C - 70 °C (2.5%/K)
Connection in parallelYes, for redundancy and increased capacity
Connection in seriesyes
Feedback voltage resistance60 V DC
Protection against overvoltage at the output (OVP)< 60 V DC
Max. capacitive loadunlimited
Active current limitationApproximately 7 A
Control deviation< 1 % (change in load, static 10 % - 90 %)
Control deviation< 2 % (change in load, dynamic 10 % - 90 %)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple< 20 mVPP
Peak switching voltages nominal load< 10 mVPP (20 MHz)
Maximum power dissipation in no-load condition5.2 W
Power loss nominal load max.21 W

Conformance/approvals

UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Recognized UL 60950-1
UL approvalsUL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Shipbuilding approvalDNV GL (EMC B)

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 25;
China RoHSFor details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C - 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
Ambient temperature (start-up type tested)-40 °C
Ambient temperature (storage/transport)-40 °C - 85 °C
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Climatic class3K3 (in acc. with EN 60721)
Degree of pollution2

Standards

EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltageEN 60950-1 (SELV)
Standard – Safety extra-low voltageEN 60204 (PELV)
Standard - Safe isolationDIN VDE 0100-410
Rail applicationsEN 50121-4

Dimensions

Width48 mm
Installation distance top/bottom (active)50 mm / 50 mm (≤ 70 °C)
Height130 mm
Depth125 mm
Width with alternative assembly122 mm
Height with alternative assembly130 mm
Depth with alternative assembly51 mm
Installation distance right/left0 mm / 0 mm (≤ 70 °C)
Installation distance left/right (active)15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom50 mm / 50 mm (≤ 70 °C)

EMC data

Electromagnetic HF fieldEN 61000-4-3
Frequency range80 MHz - 1 GHz
Frequency range1.4 GHz - 2 GHz
Test field strength10 V/m
Frequency range2 GHz - 3 GHz
Fast transients (burst)EN 61000-4-4
Input2 kV (Test Level 3 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
Signal2 kV (Test Level 4 - asymmetrical)
Surge voltage load (surge)EN 61000-4-5
Input1 kV (Test Level 2 - symmetrical)
Output1 kV (Test Level 2 - symmetrical)
Signal1 kV (Test Level 2 - asymmetrical)
CommentsCriterion A
I/O/Sasymmetrical
Frequency range0.15 MHz - 80 MHz
Voltage10 V (Test Level 3)
Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Electrostatic dischargeEN 61000-4-2
Contact discharge8 kV (Test Level 4)
Discharge in air15 kV (Test Level 4)

Connection data, input

Connection methodPluggable screw connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length8 mm
Screw threadM3

Connection data, output

Connection methodPluggable screw connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3

Input data

Nominal input voltage range24 V DC
Input voltage range18 V DC - 32 V DC
Extended input voltage range in operation14 V DC - 18 V DC (Derating)
Current consumption14 A (24 V, IBOOST)
Inrush current< 15 A (typical)
Mains buffering time> 12 ms (24 V DC)
Input fuse25 A (internal (device protection))
Type of protectionTransient surge protection
Protective circuit/componentVaristor

Connection data for signaling

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Screw threadM3

Spesso acquistati assieme


Altri articoli da PHOENIX CONTACT

Richiedi un preventivo