Inline function terminal - IB IL TEMP 2 RTD-XC-PAC - 2701217
- Produttore:
- PHOENIX CONTACT
Inline analog input terminal, extreme conditions version, complete with accessories (connector and labeling field), 2 inputs, RTD (resistance temperature detector), 2, 3, 4-conductor connection technology
Features
Two inputs for resistive temperature sensors
Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
Connection of sensors in 2, 3, and 4-wire technology
The channels are parameterized independently of one another via the bus system
Measured values can be represented in three different formats
Measured value acquisition with 16-bit resolution
Channel scout for optical channel identification
Can be used under extreme ambient conditions
Extended temperature range of -40 °C ... +70 °C (see 'Tested successfully: use under extreme ambient conditions' in the data sheet)
Coated PCBs
cULus Recognized
UL Recognized
cUL Recognized
Specifications
Depth | 71.5 mm |
---|---|
Height | 136.8 mm |
Width | 12.2 mm |
Ambient conditions | |
Permissible humidity (storage/transport) | 10 % - 95 % (non-condensing) |
Air pressure (operation) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 55 °C (Standard) |
Ambient temperature (operation) | -40 °C - 70 °C (Extended, see section 'Tested successfully: use under extreme ambient conditions' in the data sheet.) |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (non-condensing) |
Dimensions | |
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Interfaces | |
Designation | Inline local bus |
No. of channels | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Analog inputs | |
Number of inputs | 2 |
Input name | Analog RTD inputs |
Description of the input | Input for resistive temperature sensors |
Connection method | Spring-cage connection |
Connection technology | 2, 3, 4-wire |
Note regarding the connection technology | shielded |
Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors |
Linear resistance measuring range | 0 Ω - 400 Ω |
Linear resistance measuring range | 0 Ω - 4 kΩ |
Measuring principle | Successive approximation |
Measured value representation | 16 bits two's complement and other |
A/D conversion time | typ. 120 µs (per channel) |
A/D converter resolution | 16 bit (15 bit + sign bit) |
Process data update | 32 ms (both channels with 3-wire technology) |
Inline potentials | |
Designation | Communications power (UL) |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current consumption | typ. 43 mA |
Current consumption | max. 60 mA |
Designation | Supply of analog modules (UANA) |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Current consumption | typ. 11 mA |
Current consumption | max. 18 mA |
Power consumption | typ. 587 mW |
Standards and Regulations | |
Connection in acc. with standard | CUL |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Environmental Product Compliance | |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
China RoHS | No hazardous substances above threshold values |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
Electrical isolation | |
Test section | 7.5 V supply (bus logics)/24 V analog supply (analog I/O) 500 V AC 50 Hz 1 min. |
Test section | 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 1 min. |
Test section | 24 V analog supply (analog I/O) / functional earth ground 500 V AC 50 Hz 1 min. |