Type 2 surge protection plug - VAL-MS 230 ST - 2798844
- Produttore:
- PHOENIX CONTACT
Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 230 V AC
Features
CCA
EAC
cULus Recognized
GL
IECEE CB Scheme
KEMA-KEUR
CSA
ÖVE
UL Recognized
cUL Recognized
Specifications
Depth | 55.3 mm |
---|---|
Height | 52.4 mm |
Width | 17.5 mm |
Environmental Product Compliance | |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Height | 52.4 mm |
Width | 17.5 mm |
Depth | 55.3 mm |
Horizontal pitch | 1 Div. |
UL specifications | |
SPD Type | 4CA |
Maximum continuous operating voltage MCOV (L-N) | 275 V AC |
Nom. voltage | 230 V AC |
Mode of protection | L-N |
Power distribution system | Single phase |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-N) | 1910 V |
Nominal discharge current In (L-N) | 20 kA |
Connection data | |
Connection method | pluggable |
Ambient conditions | |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (10 - 500 Hz / 2.5 h / X, Y, Z) |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C - 80 °C |
Ambient temperature (storage/transport) | -40 °C - 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % - 95 % |
Protective circuit | |
Nominal voltage UN | 240/415 V AC (TN) |
Nominal voltage UN | 240/415 V AC (TT) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 275 V AC |
Residual current IPE | ≤ 0.45 mA |
Standby power consumption PC | ≤ 120 mVA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up | ≤ 1.35 kV |
Residual voltage Ures | ≤ 1.35 kV (at In) |
Residual voltage Ures | ≤ 1.1 kV (at 10 kA) |
Residual voltage Ures | ≤ 1 kV (at 5 kA) |
Residual voltage Ures | ≤ 0.9 kV (at 3 kA) |
TOV behavior at UT | 335 V AC (5 s / withstand mode) |
TOV behavior at UT | 440 V AC (120 min / safe failure mode) |
Response time tA | ≤ 25 ns |
Max. backup fuse with branch wiring | 125 A (gG) |
Standards and Regulations | |
Standards/regulations | IEC 61643-11 2011 |
Standards/regulations | EN 61643-11 2012 |