Current transducers - MCR-S-1/5-UI-DCI-NC - 2814715
- Produttore:
- PHOENIX CONTACT
MCR current transducer, programmable and configurable, for measuring direct, alternating and distorted currents, input current 0...0.2 to 0...11 A, unconfigured
Features
True r.m.s. value measurement
Device can be set via DIP switches or MCR/PI-CONF-WIN configuration software
3-way isolation
cULus Listed
EAC
cULus Recognized
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Depth | 114.5 mm |
---|---|
Height | 99 mm |
Strip Length | 8 mm |
Width | 22.5 mm |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Width | 22.5 mm |
Height | 99 mm |
Depth | 114.5 mm |
Input data | |
Input | Current measuring input |
Number of inputs | 3 |
Configurable/programmable | Yes, unconfigured |
Input current range | 0 A - 11 A (AC/DC) |
Operate threshold | 2 % (of measuring range nominal value 1/5/10 A) |
Setting range for min. input current | 0 A - 200 mA |
Setting range for max. input current | 0 A - 11 A |
Impulse form | AC, DC or distorted currents |
Overload capacity | 2 x IN (continuous) |
Surge strength | 20 x IN (1 s) |
Frequency measuring range | 15 Hz - 400 Hz |
Connection method | Screw connection |
Connection data | |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² - 2.5 mm² |
Conductor cross section flexible | 0.2 mm² - 2.5 mm² |
Conductor cross section AWG | 24 - 14 |
Conformance/approvals | |
Designation | CE |
Identification | CE-compliant |
Designation | UL, USA/Canada |
Identification | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
Identification | Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |
Ambient conditions | |
Ambient temperature (operation) | -20 °C - 60 °C |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Maximum altitude | < 2000 m |
Degree of protection | IP20 |
Noise immunity | EN 61000-6-2 |
Output data | |
Output name | Voltage output / current output |
Configurable/programmable | Yes, unconfigured |
Voltage output signal | 0 V - 10 V |
Voltage output signal | 2 V - 10 V |
Voltage output signal | -10 V - 10 V |
Voltage output signal | 0 V - 5 V |
Voltage output signal | 1 V - 5 V |
Voltage output signal | -5 V - 5 V |
Voltage output signal | 10 V - 0 V |
Voltage output signal | 10 V - 2 V |
Voltage output signal | 10 V - -10 V |
Voltage output signal | 5 V - 0 V |
Voltage output signal | 5 V - 1 V |
Voltage output signal | 5 V - -5 V |
Current output signal | 0 mA - 20 mA |
Current output signal | 4 mA - 20 mA |
Current output signal | 20 mA - 0 mA |
Current output signal | 20 mA - 4 mA |
Load/output load voltage output | > 10 kΩ |
Load/output load current output | < 500 Ω |
Switching output | |
Output name | No switching output |
Standards and Regulations | |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 |
Connection in acc. with standard | CUL |
Low Voltage Directive | Conformance with Low Voltage Directive |
Conformance | CE-compliant |
UL, USA/Canada | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
UL, USA/Canada | Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |
Power supply | |
Supply voltage range | 20 V DC - 30 V DC |
Max. current consumption | < 40 mA (without load) |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |