EMC filter surge protection device - SFP 1-20/230AC - 2859987
- Produttore:
- PHOENIX CONTACT
Device protection, according to type 3/class III, with network interference suppression filter to prevent high-frequency interference voltages, for 1-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with remote indication contact.
Features
Can be installed in industrial environments
Combined protective circuit for absorbing transient surge voltages and high-frequency interference voltages
Thermal monitoring of the protective circuit
Disconnection status signaled via floating remote indication contact
Integrated power display switches off automatically when there is a malfunction due to overload.
EAC
Specifications
Depth | 79 mm |
---|---|
Height | 86.6 mm |
Strip Length | 7 mm |
Width | 112 mm |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Height | 86.6 mm |
Width | 112 mm |
Depth | 79 mm |
Connection data | |
Connection method | Screw terminal blocks |
Conductor cross section flexible | 2.5 mm² - 4 mm² |
Conductor cross section solid | 2.5 mm² - 6 mm² |
Conductor cross section AWG | 14 - 10 |
Screw thread | M3 |
Tightening torque | 0.5 Nm - 0.6 Nm |
Tightening torque | 4.5 lbf-in. - 5.5 lbf-in. |
Stripping length | 8 mm |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 70 °C |
Ambient temperature (storage/transport) | -25 °C - 70 °C |
Permissible humidity (operation) | 5 % - 95 % |
Indicator/remote signaling | |
Switching function | PDT contact |
Operating voltage | 12 V AC - 250 V AC |
Operating voltage | 250 V DC (250 mA DC) |
Operating current | 100 mA AC - 1 A AC |
Operating current | 1 A DC (48 V DC) |
Connection method | Pluggable screw connection |
Conductor cross section flexible | 0.14 mm² - 1.5 mm² |
Conductor cross section solid | 0.14 mm² - 1.5 mm² |
Conductor cross section AWG | 26 - 16 |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Protective circuit | |
Nominal voltage UN | 240 V AC (TN) |
Nominal voltage UN | 240 V AC (TT - only in use with RCD) |
Nominal voltage UN | 240 V AC (IT - only in use with RCD) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 264 V AC |
Rated load current IL | 20 A (40 °C) |
Residual current IPE | ≤ 0.6 mA |
Nominal discharge current In (8/20) µs | 5 kA |
Standby power consumption PC | ≤ 25 VA (at UREF) |
Standby power consumption PC | ≤ 27.5 VA (at UC) |
Reference test voltage UREF | 264 V AC |
Combination wave UOC | 10 kV (5 kA) |
Voltage protection level Up | ≤ 1 kV |
TOV behavior at UT (L-N) | 350 V AC (5 s / withstand mode) |
TOV behavior at UT (L-N) | 457 V AC (120 min / safe failure mode) |
TOV behavior at UT (L-PE) | 457 V AC (5 s / withstand mode) |
TOV behavior at UT (L-PE) | 350 V AC (120 min / withstand mode) |
TOV behavior at UT (L-PE) | 1464 V AC (200 ms / safe failure mode) |
TOV behavior at UT (N-PE) | 1200 V AC (200 ms / safe failure mode) |
Response time tA | ≤ 25 ns |
Capacity (L-N) | 1 µF ±10 % |
Capacity (L-N) | 10 nF ±10 % (X2-275 V) |
Capacity (L-PE) | 2.2 nF ±20 % (Y2-250 V) |
Capacity (L-PEN) | 2.2 nF ±20 % (Y2-250 V) |
Max. required back-up fuse | 20 A (MCB B/general purpose) |
Max. required back-up fuse | 16 A (IT - MCB B/general purpose) |
Input attenuation aE, sym. | 20 dB (≥ 100 kHz / 50 Ω) |
Input attenuation aE, asym. | 30 dB (≥ 1 MHz / 50 Ω) |
Short-circuit current rating ISCCR | 5 kA AC (TN/TT) |
Short-circuit current rating ISCCR | 1 kA AC (IT) |
Protective circuit, filter | |
Discharge resistance | 820 kΩ |