Inline terminal - IB IL 24 DI 4-PAC - 2861234
- Produttore:
- PHOENIX CONTACT
Inline, Digital input terminal, Digital inputs: 4, 24 V DC, connection method: 3-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
Features
4 digital inputs
Connection of sensors in 2 and 3-wire technology
Maximum permissible load current per sensor: 250 mA
Maximum permissible load current from the terminal: 1 A
BV
BSH
cULus Listed
EAC
ATEX
LR
RINA
DNV GL
ABS
UL Listed
cUL Listed
UL Recognized
Specifications
Depth | 71.5 mm |
---|---|
Height | 140.5 mm |
Width | 12.2 mm |
Environmental Product Compliance | |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Width | 12.2 mm |
Height | 140.5 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Interfaces | |
Designation | Inline local bus |
No. of channels | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Digital inputs | |
Input name | Digital inputs |
Description of the input | EN 61131-2 type 1 |
Connection method | Spring-cage connection |
Connection technology | 3-wire |
Number of inputs | 4 |
Typical response time | < 1 ms |
Protective circuit | Short-circuit and overload protection |
Nominal input voltage UIN | 24 V DC |
Nominal input current at UIN | min. 3 mA (at nominal voltage) |
Input voltage | 24 V DC |
Input voltage range "0" signal | -3 V DC - 5 V DC |
Input voltage range "1" signal | 15 V DC - 30 V DC |
Inline potentials | |
Designation | Communications power (UL) |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current consumption | max. 40 mA |
Power consumption | max. 0.3 W |
Designation | Segment circuit supply (US) |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Current consumption | max. 1 A |
Current consumption | 0 A |
Ambient conditions | |
Permissible humidity (storage/transport) | 10 % - 95 % (non-condensing) |
Air pressure (operation) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Air pressure (operation) | 80 kPa - 106 kPa (up to 3000 m above sea level, in ATEX Zone 2) |
Air pressure (storage/transport) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 55 °C |
Ambient temperature (storage/transport) | -25 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (non-condensing) |
Standards and Regulations | |
Connection in acc. with standard | CUL |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Electrical isolation | |
Test section | 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min. |
Test section | 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Test section | 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 500 min. |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |