Inline terminal - IB IL AI 2/SF-PAC - 2861302
- Produttore:
- PHOENIX CONTACT
Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection method: 2-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
Features
2 analog single-ended signal inputs for the connection of either voltage or current signals
Connection of sensors in 2-wire technology
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Voltage ranges: 0 V ... 10 V, ±10 V
Channels are parameterized independently of one another via the bus system
Measured values can be represented in four different formats
Resolution depends on the representation format and the measuring range
Process data update of both channels within a max. of 1.5 ms
BV
BSH
cULus Listed
EAC
ATEX
LR
RINA
DNV GL
ABS
UL Listed
cUL Listed
UL Recognized
Specifications
Depth | 71.5 mm |
---|---|
Height | 136.8 mm |
Width | 12.2 mm |
Electrical isolation | |
Test section | 7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC 50 Hz 1 min. |
Test section | 7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min. |
Test section | I/O / functional earth ground 500 V AC 50 Hz 1 min. |
Dimensions | |
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Interfaces | |
Designation | Inline local bus |
No. of channels | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Analog inputs | |
Description of the input | Single-ended inputs, voltage or current |
Input name | Analog inputs |
Number of inputs | 2 |
Connection method | Inline shield connector |
Connection technology | 2-wire |
Note regarding the connection technology | shielded |
A/D conversion time | typ. 120 µs (per channel) |
Limit frequency (3 dB) | 40 Hz |
Type of protection | Surge protection |
Data formats | IB IL, IB ST, IB RT, standardized representation |
Measuring principle | Successive approximation |
Measured value resolution | 16 bits (15 bits + sign bit) |
Measured value representation | 16 bit two's complement |
Current input signal | 0 mA - 20 mA |
Current input signal | 4 mA - 20 mA |
Current input signal | -20 mA - 20 mA |
Input resistance current input | 50 Ω (Shunt) |
Voltage input signal | 0 V - 10 V |
Voltage input signal | -10 V - 10 V |
Input resistance of voltage input | > 220 kΩ |
Common mode voltage range signal - ground | 40 V (between current input and functional earth ground) |
Ambient conditions | |
Permissible humidity (storage/transport) | 10 % - 95 % (non-condensing) |
Air pressure (operation) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Air pressure (operation) | 80 kPa - 106 kPa (up to 3000 m above sea level, in ATEX Zone 2) |
Air pressure (storage/transport) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 55 °C |
Ambient temperature (storage/transport) | -25 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (non-condensing) |
Inline potentials | |
Designation | Communications power (UL) |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current consumption | typ. 45 mA |
Current consumption | max. 60 mA |
Designation | Supply of analog modules (UANA) |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Current consumption | typ. 13 mA |
Current consumption | max. 18 mA |
Power consumption | typ. 662 mW |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
China RoHS | No hazardous substances above threshold values |
Standards and Regulations | |
Connection in acc. with standard | CUL |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |