Inline function terminal - IB IL TEMP 4/8 RTD-PAC - 2863915
- Produttore:
- PHOENIX CONTACT
Inline analog input terminal, complete with accessories (connector and labeling field), 8 channels, RTD (resistance temperature detector), 2, 3-wire connection method
Features
Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
8 inputs for resistive temperature sensors and linear resistors up to 20 kΩ
Connection of sensors in 2 and 3-wire technology
Communication either via process data or parameter channel (PCP)
The channels are parameterized independently of one another via the bus system
Robust inputs ideal for use in harsh industrial environments with electromagnetic interference
Measured values can be represented in three different formats
Temperature and resistance measurement in the millisecond range
Diagnostic and status indicators
BV
BSH
cULus Listed
EAC
LR
RINA
DNV GL
ABS
UL Listed
cUL Listed
Specifications
Depth | 71.5 mm |
---|---|
Height | 136.8 mm |
Width | 48.8 mm |
Electrical isolation | |
Test section | 7.5 V supply (bus logic)/±15.5 V, ±5 V analog supply (analog I/O) 500 V AC 50 Hz 1 min. |
Test section | 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 1 min. |
Test section | ±15.5 V, ±5 V analog supply (analog I/O)/functional earth ground 500 V AC 50 Hz 1 min. |
Dimensions | |
Width | 48.8 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Analog inputs | |
Number of inputs | 8 |
Input name | Analog RTD inputs |
Description of the input | Input for resistive temperature sensors |
Connection method | Spring-cage connection |
Connection technology | 2, 3-conductor |
Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors |
Linear resistance measuring range | 0 Ω - 400 Ω |
Linear resistance measuring range | 0 Ω - 20 kΩ |
Measuring principle | Successive approximation |
Measured value representation | 16 bits (15 bits + sign bit) |
A/D conversion time | max. 10 µs |
Process data update | 6 ms (Up to 230 ms possible depending on operating mode) |
Data formats | IB IL, IB ST, S7 compatible |
Interfaces | |
Designation | Inline local bus |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Transmission physics | Copper |
Ambient conditions | |
Air pressure (operation) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 55 °C |
Ambient temperature (storage/transport) | -25 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 10 % - 95 % (according to DIN EN 61131-2) |
Inline potentials | |
Designation | Communications power (UL) |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current consumption | typ. 75 mA |
Current consumption | max. 100 mA |
Designation | Supply of analog modules (UANA) |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Current consumption | typ. 28 mA |
Current consumption | max. 55 mA |
Power consumption | typ. 1.24 W |
Standards and Regulations | |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Environmental Product Compliance | |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
China RoHS | No hazardous substances above threshold values |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |