Temperature measuring transducer - MINI MCR-SL-PT100-UI-200-NC - 2864370
- Produttore:
- PHOENIX CONTACT
MCR temperature transducer, configurable, for Pt 100 temperature sensors, with screw-connection, not configured
Features
Power supply possible via the foot element (TBUS)
Optimized temperature measuring range of -50°C to +200°C for increased accuracy
For 2, 3 or 4-wire Pt 100 sensors according to IEC 60751
Error indication via diagnostic LED and analog signal
Pt 100 signals to create standard signals
3-way isolation
Highly-compact temperature transducer for electrical isolation, conversion, amplification, and filtering of
Input and output signals can be configured via DIP switches
cULus Listed
cULus Recognized
ATEX
EAC Ex
GL
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Depth | 101.2 mm |
---|---|
Height | 93.1 mm |
Strip Length | 12 mm |
Width | 6.2 mm |
Ambient conditions | |
Ambient temperature (operation) | -20 °C - 65 °C |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (non-condensing) |
Degree of protection | IP20 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Power supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Max. current consumption | < 21 mA (at 24 V DC) |
Power consumption | < 500 mW |
Dimensions | |
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 101.2 mm |
Output data | |
Number of outputs | 1 |
Configurable/programmable | Yes |
Voltage output signal | 0 V - 10 V |
Voltage output signal | 10 V - 0 V |
Voltage output signal | 0 V - 5 V |
Voltage output signal | 1 V - 5 V |
Current output signal | 0 mA - 20 mA |
Current output signal | 4 mA - 20 mA |
Current output signal | 20 mA - 0 mA |
Current output signal | 20 mA - 4 mA |
Max. output voltage | approx. 12.5 V |
Max. output current | 23 mA |
Short-circuit current | approx. 10 mA |
Load/output load voltage output | > 10 kΩ |
Load/output load current output | < 500 Ω (at 20 mA) |
Ripple | < 20 mVPP (at 500 Ω) |
Ripple | < 20 mVPP (at 10 kΩ) |
Connection data | |
Connection method | Screw connection |
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² - 2.5 mm² |
Conductor cross section flexible | 0.2 mm² - 2.5 mm² |
Conductor cross section AWG | 26 - 12 |
Standards and Regulations | |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Standards/regulations | EN 61000-4-4 |
Standards/regulations | EN 61000-4-5 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D T5 |
GL | GL EMC 2 D |
EMC data | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 10 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Input data | |
Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) |
Sensor input current | 1 mA (constant) |
Temperature measuring range | -50 °C - 200 °C |
Connection technology | 2, 3, 4-wire |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |