Miniature solid-state relay - OPT-24DC/ 48DC/100 - 2966618
- Produttore:
- PHOENIX CONTACT
Plug-in miniature solid-state relay, input solid-state relay, 1 N/O contact, input: 24 V DC, output: 3 - 48 V DC/100 mA
Features
Vibration and shock resistant
RT III-proof (wash-proof)
Wear-free and durable
Zero voltage switch at AC output
Can be soldered on PCB
Switching power of up to 24 V DC/5 A
EAC
PRS
GL
UL Recognized
cUL Recognized
Specifications
Depth | 15 mm |
---|---|
Height | 28 mm |
Width | 5 mm |
Dimensions | |
Width | 5 mm |
Height | 28 mm |
Depth | 15 mm |
Input data | |
Switching threshold "0" signal, voltage | ≤ 10 V |
Switching threshold "1" signal voltage | ≥ 16 V |
Typical input current at UN | 7 mA |
Typical response time | 20 µs (at UN) |
Typical turn-off time | 300 µs (at UN) |
Transmission frequency | 300 Hz |
Power dissipation for nominal condition | 0.17 W |
Nominal input voltage UN | 24 V DC |
Input voltage range in reference to UN | 0.8 - 1.2 |
Input voltage range | 19.2 V DC - 28.8 V DC |
Output data | |
Output voltage range | 3 V DC - 48 V DC |
Limiting continuous current | 100 mA |
Voltage drop at max. limiting continuous current | ≤ 1 V |
Output circuit | 2-wire, floating |
Type of protection | Reverse polarity protection |
Type of protection | Surge protection |
Standards and Regulations | |
Connection in acc. with standard | CUL |
Designation | Standards/regulations |
Standards/regulations | IEC 60664 |
Standards/regulations | EN 50178 |
Insulation | Basic insulation |
Pollution degree | 2 |
Overvoltage category | III |
Ambient conditions | |
Ambient temperature (operation) | -25 °C - 60 °C |
Ambient temperature (storage/transport) | -25 °C - 70 °C |
Degree of protection | RT III |
Environmental Product Compliance | |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
China RoHS | No hazardous substances above threshold values |