ET 200SP, DI 8X24VDC ST
- Produttore:
- SIEMENS
- Prezzo (IVA esclusa)
- € 39.36
- Codice Nuova Elva
- 6ES71316BF000BA0
- Codice produttore
- 6ES7131-6BF00-0BA0
- Disponibilità
- Invia RdO
Simatic ET 200SP, Digital Input Module, DI 8X 24VDC Standard, Fits to BU-Type A0, Color Code CC01, Module Diagnosis
Specifications
Connection Type | Push-In Terminal |
---|---|
Depth | 58 mm |
Height | 73 mm |
Input Voltage | 24 V |
IP Rating | IP20 |
Max. Voltage | 28.8 V |
Number of Inputs | 8 |
Voltage | 24 V |
Weight | .037 kg |
Width | 15 mm |
Specifications | |
Net Weight in Kg | 0.037 |
Design of the sensor connectable 2-wire transmitter | Yes |
Wire length at digital input shielded maximum [m] | 1000 |
Wire length at digital input unshielded maximum [mm] | 600000 |
Diagnostics function | Yes |
Diagnostics function Cable break | Yes |
Diagnostics function Cable break Note | Module-wise |
Diagnostics function Diagnostics information readable | Yes |
Diagnostics function Monitoring of the mains voltage of the electronic | Yes |
Diagnostics function Short-circuit detection | Yes |
Diagnostics function Short-circuit detection Note | Module-wise |
Digital input version Type 1 acc. to IEC 61131 | Yes |
Digital input version Type 2 acc. to IEC 61131 | No |
Supplier | Siemens AG |
Display version for diagnostic function: Status display expansion modules module diagnostics (traffic light green-red-yellow or DIAG red/green) | Yes |
Display version for diagnostic function: Status display expansion modules module diagnostics (traffic light green-red-yellow or DIAG red/green) Note | green/red DIAG LED |
Display version for diagnostic function: Status display transmission channel channel diagnostics LED | No |
Display version for diagnostic function: Status display transmission channel channel status LED | Yes |
Display version for diagnostic function: Status display transmission channel channel status LED Note | Green LED |
Display version for diagnostic function: Supply voltage monitoring Power LED | Yes |
Display version for diagnostic function: Supply voltage monitoring Power LED Note | green PWR LED |
Equipment marking acc. to DIN EN 81346-2 | K |
Explosion protection category for dust | No |
Explosion protection category for gas | ATEX II 3 G Ex nA II T4 ... T5 |
Order number | 6ES7131-6BF00-0BA0 |
Explosion protection marking for intrinsic safety of related equipment EEx ia | No |
Explosion protection marking for intrinsic safety of related equipment EEx ib | No |
Firmware version | V1.1 |
Galvanic isolation at the universal inputs between the channels | No |
Galvanic isolation at the universal inputs between the channels and backing bus | Yes |
Galvanic isolation at the universal inputs between the channels and voltage supply of the electronics | No |
GSD version/revision with PROFIBus required | GSD Revision 5 |
GSD version/revision with PROFINET required | GSDML V2.3 |
Height [mm] | 73 |
Input current at digital input for signal <1> typical [mA] | 2.5 |
address range memory per module maximum [byte] | 1 |
Input voltage at digital input at DC Rated value [V] | 24 |
Mounting type front mounting | Yes |
Mounting type rack mounting | Yes |
Mounting type rail mounting | Yes |
Mounting type wall mounting | No |
Number of digital inputs | 8 |
Number of interfaces acc. to PROFINET | 0 |
Number of interfaces acc. to RS 485 | 0 |
Number of outputs for encoder supply | 8 |
Operating mode as counter | No |
address range memory per module maximum Note | =+ 1 byte for QI information |
Operating mode as digital input | Yes |
Operating mode oversampling | No |
Operating voltage as input voltage maximum permissible [V] | 30 |
Operating voltage as input voltage minimum permissible [V] | -30 |
Output current with 24 V encoder supply maximum [mA] | 700 |
Output current with 24 V encoder supply maximum Note | Total current of all encoders |
Output voltage for encoder supply minimum [V] | 19.2 |
Power loss [W] typical [mW] | 1000 |
product brandname | Simatic DP |
Product category | Digital module input |
Alert function Diagnostics alarm | Yes |
Product extension required separate bus coupler for fieldbus connection | Yes |
Product family | ET 200SP |
Product feature of the firmware version can be updated | Yes |
Product function at alarm inputs at rated input voltage parameterizable input delay time | No |
Product function at the inputs for counters or technological functions at rated input voltage parameterizable input delay time | No |
Product function at the standard inputs at rated input voltage parameterizable input delay time | Yes |
Product function at the standard inputs at rated input voltage parameterizable input delay time Note | 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) |
Product function for diagnostic function: Encoder supply monitoring parameterizable | Yes |
Product function for diagnostic function: Encoder supply monitoring parameterizable Note | Module-wise |
Product function for diagnostic function: Supply voltage monitoring parameterizable | Yes |
Color coding of labeling plates for module-specific use usable | CC01 |
Product function for encoder supply Short-circuit protection | Yes |
Product function for encoder supply Short-circuit protection Note | per module |
Product function I&M data | Yes |
Product function I&M data Note | I&M0 to I&M3 |
Product function MSI | No |
Product function pulse stretching | No |
Product function Reverse polarity protection | Yes |
Product function with 24 V encoder supply Short-circuit protection | Yes |
Product type designation | ET 200SP, DI 8x 24 V DC ST, PU 1 |
Product type designation of the racks usable | BU type A0 |
Consumed current maximum [mA] | 50 |
Protection class IP | IP20 |
Protocol is supported PROFIBus protocol | No |
Protocol is supported PROFINET IO protocol | No |
Protocol is supported PROFIsafe protocol | No |
Quiescent current of the 2-wire transducer maximum permissible [mA] | 1.5 |
Software version for PCS 7 application required | V8.1 SP1 |
Software version with STEP 7 required | V5.5 SP3 / - |
Software version with STEP 7 in the TIA Portal required | V11 SP2 / V13 |
Suitability for use safety-related function | No |
Supply voltage at DC Rated value [V] | 24 |
Depth [mm] | 58 |
Supply voltage at DC rated value maximum [V] | 28.8 |
Supply voltage at DC rated value minimum [V] | 19.2 |
Supply voltage for encoder supply 24 V | Yes |
Type of electrical connection | Push-in terminal |
Type of isolation test | 707 V DC (type test) |
Type of voltage at digital input | DC |
Type of voltage of the supply voltage | DC |
Value range of the input voltage at digital input for signal <0> detection | -30 to +5V |
Value range of the input voltage at digital input for signal <1> detection | =+11 to +30V |
Width [mm] | 15 |
Delivery Information | |
Export Control Regulations | AL : N / ECCN : N |
Standard lead time ex-works | 1 Day/Days |
Net Weight (lb) | 0.082 lb |
Product Dimensions (W x L x H) | Not available |
Packaging Dimension | 2.559 x 3.031 x 0.906 |
Package size unit of measure | in |
Quantity Unit | 1 Piece |
Packaging Quantity | 1 |
Additional Product Information | |
EAN | 4025515080770 |
UPC | 40892933406 |
Commodity Code | 85389091 |
LKZ_FDB/ CatalogID | ST76 |
Product Group | 4520 |
Country of origin | Germany |
RoHS Compliance | Since: 01/31/2012 |
Returnable | Yes |
Obligation Category for taking back electrical and electronic equipment after use | No obligation to take back electrical and electronic equipment after use |