SINAMICS PM240-2 IP20-FSA-A-400V-3KW
- Produttore:
- SIEMENS
- Prezzo (IVA esclusa)
- € 972.00
- Codice Nuova Elva
- 6SL32101PE180AL1
- Codice produttore
- 6SL3210-1PE18-0AL1
- Disponibilità
- Invia RdO
SINAMICS POWER MODULE PM240-2 WITH BUILT IN CL. A FILTER WITH BUILT IN BRAKING CHOPPER 3AC380-480V +10/-10% 47-63HZ OUTPUT HIGH OVERLOAD: 2,2KW FOR 200% 3S,150% 57S,100% 240S AMBIENT TEMP -10 TO +50 DEG C OUTPUT LOW OVERLOAD: 3KW FOR 150% 3S,110% 57S,100% 240S AMBIENT TEMP -10 TO +40 DEG C 196 X 73 X 165 (HXWXD), FSA PROTECTION IP20 WITHOUT CONTROL UNIT AND PANEL APPROVED FOR CU FIRMWARE- VERSION V4.6
Specifications
Certifications | C-Tick |
---|---|
Depth | 165 mm |
Height | 196 mm |
Weight | 1.5 kg |
Width | 73 mm |
Specifications | |
1 m measuring surface sound pressure level maximum [dB] | 71.6 |
Ambient temperature with low overload during operation minimum [°C] | -5 |
Relative negative tolerance for line voltage [%] | -10 |
Relative negative tolerance of line frequency [%] | 5 |
Relative positive tolerance for line voltage [%] | 10 |
Relative positive tolerance of line frequency [%] | 5 |
Relative power loss [W] of the CDM at the CDM operating point (0/100) [%] | 1.6 |
Relative power loss [W] of the CDM at the CDM operating point (0/25) [%] | 1.06 |
Relative power loss [W] of the CDM at the CDM operating point (0/50) [%] | 1.21 |
Relative power loss [W] of the CDM at the CDM operating point (50/100) [%] | 1.82 |
Relative power loss [W] of the CDM at the CDM operating point (50/25) [%] | 1.1 |
Relative power loss [W] of the CDM at the CDM operating point (50/50) [%] | 1.3 |
Ambient temperature [°F] during storage maximum [°F] | 131 |
Relative power loss [W] of the CDM at the CDM operating point (90/100) [%] | 2.17 |
Relative power loss [W] of the CDM at the CDM operating point (90/50) [%] | 1.43 |
Resistance to biologically active substances during operation | Class 3B1 according to EN 60721-3-3 |
Resistance to biologically active substances during storage | Class 1B1 according to EN 60721-3-1 |
Resistance to biologically active substances during transport | Class 2B1 to EN 60721‑3‑2 |
Resistance to chemically active substances during operation | Class 3C2 according to EN 60721-3-3 |
Resistance to chemically active substances during storage | Class 1C2 according to EN 60721-3-1 |
Resistance to chemically active substances during transport | Class 2C2 according to EN 60721-3-3 |
Shock acceleration during operation acc. to EN 60068-2-27 [m/s2] | 147 |
Shock acceleration during operation Note | (15 × g)/11 ms |
Ambient temperature [°F] during storage maximum Note | Class 1K3 acc. to EN 60721-3-1 |
Shock acceleration during transport acc. to EN 60721-3-2 Note | Class 2M3 |
Short-time withstand current (SCCR) of the entire control cabinet acc. to UL 508A [kA] | 65 |
Standard for EMC acc. to EN 61800-3 | The EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter. |
Supplied active power at rated value of output voltage with high overload [kW] | 2.2 |
Supplied active power at rated value of output voltage with low overload [kW] | 3 |
Supplied active power [hp] at rated value of output voltage with high overload [hp] | 3 |
Supplied active power [hp] at rated value of output voltage with low overload [hp] | 4 |
Supply requirements for short circuit voltage | u K < 1 % line reactor recommended |
Supply voltage maximum [V] | 480 |
Supply voltage minimum [V] | 380 |
Ambient temperature [°F] during storage minimum [°F] | -13 |
Touch protection acc. to EN 61800-5-1 | Assuming use as prescribed |
Type of converter | U converter |
Type of cooling | Internal air cooling |
Type of cooling Note | Power units with intensified air cooling thanks to integrated fan |
Type of duty cycle duration with high overload | 1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of 300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time of 300 s |
Type of duty cycle duration with low overload | 1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s 1.5 × rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s |
Type of electrical connection for mains supply line | Plug-in screw terminals |
Type of electrical connection for PE conductor | Plug-in screw terminals |
Type of electrical connection of the motor | Plug-in screw terminals |
Type of voltage of the input voltage | AC |
Ambient temperature [°F] during transport maximum [°F] | 158 |
Type of voltage of the output voltage | AC |
Vibration frequency during transport acc. to EN 60721-3-2 Note | Class 2M3 |
Vibration frequency with constant acceleration during operation acc. to EN 60068-2-6 maximum [Hz] | 200 |
Vibration frequency with constant acceleration during operation acc. to EN 60068-2-6 maximum Note | constant acceleration = 9.81 m/s2 (1 × g) |
Vibration frequency with constant acceleration during operation acc. to EN 60068-2-6 minimum [Hz] | 58 |
Vibration frequency with constant deflection during operation acc. to EN 60068-2-6 maximum [Hz] | 58 |
Vibration frequency with constant deflection during operation acc. to EN 60068-2-6 maximum Note | constant deflection 0.075 mm |
Vibration frequency with constant deflection during operation acc. to EN 60068-2-6 minimum [Hz] | 10 |
Width [mm] | 73 |
Wire length for motor shielded maximum [m] | 50 |
Ambient temperature [°F] during transport maximum Note | Class 2K4 according to EN 60721-3-2 |
Wire length for motor unshielded maximum [m] | 100 |
Ambient temperature [°F] during transport minimum [°F] | -40 |
Ambient temperature [°F] with high overload during operation maximum [°F] | 122 |
Ambient temperature [°F] with high overload during operation minimum [°F] | 23 |
Ambient temperature [°F] with low overload during operation maximum [°F] | 104 |
Ambient temperature during operation acc. to EN 60721-3-3 Note | Class 3K3, condensation, splashwater, and ice formation not permitted (EN 60204, Part 1) |
Ambient temperature [°F] with low overload during operation minimum [°F] | 23 |
Apparent power output rated value [kVA] | 5.3 |
AWG number as coded connectable conductor cross section for mains supply line maximum | 14 |
AWG number as coded connectable conductor cross section for mains supply line minimum | 16 |
AWG number as coded connectable conductor cross section for motor supply line maximum | 14 |
AWG number as coded connectable conductor cross section for motor supply line minimum | 16 |
Brake version | DC braking, compound braking, resistance braking with integrated brake chopper (for size FSGX optional) |
Certificate of suitability | UL, cUL, CE, C-Tick (RCM), SEMI F47 |
Certificate of suitability for CE marking | Low-voltage directive 2006/95/EC |
Connectable conductor cross-section for mains supply line maximum [mm2] | 2.5 |
Ambient temperature during storage maximum [°C] | 55 |
Connectable conductor cross-section for mains supply line minimum [mm2] | 1.5 |
Connectable conductor cross-section for motor supply line maximum [mm2] | 2.5 |
Connectable conductor cross-section for motor supply line minimum [mm2] | 1.5 |
Consumed current from supply voltage for Control Unit at DC at 24 V [A] | 1 |
Cooling air flow [m3/s] | 0.005 |
Degree of pollution | 2 according to EN 61800-5-1 |
Depth [mm] | 165 |
Design of the converter | FSA |
Design of the net filter | Class A |
Displacement factor cos phi 1 | 0.95 |
Ambient temperature during storage minimum [°C] | -25 |
Efficiency | 0.96 |
Electrical input frequency maximum [Hz] | 63 |
Electrical input frequency minimum [Hz] | 47 |
Electrical output frequency [Hz] | 50 |
Electrical output frequency for U/f control maximum [Hz] | 550 |
Electrical output frequency for U/f control minimum [Hz] | 0 |
Electrical output frequency for vector control maximum [Hz] | 200 |
Electrical output frequency for vector control minimum [Hz] | 0 |
Equipment marking acc. to DIN EN 81346-2 | Q |
Height [mm] | 196 |
Ambient temperature during transport maximum [°C] | 70 |
IE class of the CDM | IE2 |
Input current with high overload rated value [A] | 8.8 |
Input current with low overload rated value [A] | 10.1 |
Installation altitude at height above sea level without power reduction maximum [m] | 1000 |
Installation environment regarding EMC environment A | yes |
Installation environment regarding EMC environment B | no |
Mounting type Through-hole technology | no |
Net weight [kg] | 1.5 |
Operating resource protection class acc. to EN 61800-5-1 | Class I (with protective bonding circuit) and Class III (PELV) |
Output current rated value maximum [A] | 11.8 |
Ambient temperature during transport minimum [°C] | -40 |
Output current with high overload rated value [A] | 5.9 |
Output current with low overload rated value [A] | 7.7 |
Output current without overload rated value [A] | 7.7 |
Output voltage rated value [V] | 400 |
Output voltage in percent related to the input voltage maximum [%] | 95 |
Output voltage in percent related to the input voltage minimum [%] | 0 |
Phase number of the input voltage | 3 |
Phase number of the output voltage | 3 |
Power factor | 0.85 |
Power loss [W] maximum [kW] | 0.12 |
Ambient temperature with high overload during operation maximum [°C] | 50 |
Power loss [W] of the CDM at the CDM operating point (0/100) [W] | 85 |
Power loss [W] of the CDM at the CDM operating point (0/25) [W] | 57 |
Power loss [W] of the CDM at the CDM operating point (0/50) [W] | 65 |
Power loss [W] of the CDM at the CDM operating point (50/100) [W] | 97 |
Power loss [W] of the CDM at the CDM operating point (50/25) [W] | 59 |
Power loss [W] of the CDM at the CDM operating point (50/50) [W] | 69 |
Power loss [W] of the CDM at the CDM operating point (90/100) [W] | 116 |
Power loss [W] of the CDM at the CDM operating point (90/50) [W] | 76 |
Power loss [W] of the CDM in standby mode [W] | 12 |
product brand name | SINAMICS |
Ambient temperature with high overload during operation minimum [°C] | -5 |
Product component Brake chopper | yes |
Product component Line filter | yes |
Product designation | PM240-2 |
Product function 4 quadrant operation | no |
Product type designation | G120 |
Protection class IP | IP20 |
Protection function for converter Temperature monitoring | yes |
Protection function for motor Temperature monitoring | yes |
Protection function Ground fault protection | yes |
Protection function Overload protection | yes |
Ambient temperature with low overload during operation maximum [°C] | 40 |
Protection function Overvoltage protection | yes |
Protection function parameter lock | yes |
Protection function Short-circuit protection | yes |
Protection function Stall protection | yes |
Protection function undervoltage protection | yes |
Protection function with blocked rotor | yes |
Pulse frequency rated value [kHz] | 4 |
Ratio of converter losses/reference converter losses at the CDM operating point (90/100) | 67.71 |
Relative humidity without condensation during operation maximum [%] | 95 |
Relative humidity without condensation during operation maximum Note | RH, condensation not permitted |
Delivery Information | |
Export Control Regulations | AL : 9I999KP / ECCN : N |
Delivery Time | 3 Day/Days |
Net Weight (lb) | 3,307 lb |
Product Dimensions (W x L x H) | Not available |
Packaging Dimension | 3,543 x 7,283 x 11,024 |
Package size unit of measure | in |
Quantity Unit | 1 Piece |
Packaging Quantity | 1 |
Additional Product Information | |
EAN | 4042948666012 |
UPC | 887621779993 |
Commodity Code | 85044084 |
LKZ_FDB/ CatalogID | D11.1SD |
Product Group | 9772 |
Country of origin | Great Britain |
RoHS Compliance | Since: 07/01/2006 |
Returnable | No |
Obligation Category for taking back electrical and electronic equipment after use | No obligation to take back electrical and electronic equipment after use |