Prospective Line Isc | 5 kA |
---|
4 Quadrant Operation Possible | true |
---|
Apparent Power | 2.2 kVA 480 V normal duty) || 2.2 kVA 480 V heavy duty) |
---|
Net Weight | 1.7 kg |
---|
With Safety Function Safe Direction (Sdi) | false |
---|
Type Of Polarization | no impedance |
---|
Relay Output Type | relay outputs R1A || relay outputs R1C 100000 cycles || relay outputs R2A || relay outputs R2C 100000 cycles |
---|
Switching Frequency | 2...16 kHz adjustable || 14...16 kHz with derating factor |
---|
Maximum Transient Current | 3.1 A 60 s normal duty) || 3.3 A 60 s heavy duty) || 3.8 A 2 s normal duty) || 4 A 2 s heavy duty) |
---|
Analogue Input Number | 2 |
---|
Motor Slip Compensation | can be suppressed || not available in permanent magnet motor law || automatic whatever the load || adjustable |
---|
Power Dissipation In W | natural convection 28 W 380 V 4 kHz heavy duty) || forced convection 28 W 380 V 4 kHz heavy duty) || natural convection 33 W 380 V 4 kHz normal duty) || forced convection 33 W 380 V 4 kHz normal duty) |
---|
Discrete Output Number | 2.0 |
---|
With Safety Function Safe Position (Sp) | false |
---|
Method Of Access | slave Modbus RTU |
---|
With Safety Function Safely Limited Position (Slp) | false |
---|
With Safety Function Safe Operating Stop (Sos) | false |
---|
Number Of Addresses | 1-247 |
---|
Discrete Input Number | 5 |
---|
With Sft Fct Safe Stop 2 (Ss2) | false |
---|
With Safety Function Safe Stop 1 (Ss1) | true |
---|
Width | 85.0 mm |
---|
Line Current | 2.6 A 380 V normal duty) || 2.1 A 480 V normal duty) || 3.4 A 380 V heavy duty) || 2.6 A 480 V heavy duty) |
---|
Transmission Rate | 4.8 kbit/s || 9.6 kbit/s || 19.2 kbit/s || 38.4 kbit/s |
---|
Depth | 232.5 mm |
---|
Analogue Input Type | AI1 software-configurable current 0...20 mA 250 Ohm 12 bits || AI1 software-configurable temperature probe or water level sensor || AI1 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI2 software-configurable voltage - 10...10 V DC 31.5 kOhm 12 bits |
---|
Electrical Connection | line side screw terminal 1.5...4 mm² AWG 14...AWG 12 || DC bus screw terminal 4...6 mm² AWG 12...AWG 10 || motor screw terminal 1.5...4 mm² AWG 14...AWG 12 || control screw terminal 0.2...2.5 mm² AWG 24...AWG 12 |
---|
Maximum Output Frequency | 0.599 kHz |
---|
With Safety Function Safe Brake Management (Sbc/Sbt) | true |
---|
Height | 270.0 mm |
---|
Acceleration And Deceleration Ramps | S, U or customized || linear adjustable separately from 0.01...9999 s |
---|
Maximum Output Voltage | 480 V |
---|
Base Load Current At High Overload | 2.2 A |
---|
Line Current | 2.6 A 480 V without line choke heavy duty) || 2.6 A 380 V with external line choke normal duty) || 2.1 A 480 V with external line choke normal duty) || 1.9 A 380 V with external line choke heavy duty) || 1.6 A 480 V with external line choke heavy duty) || 3.4 A 380 V without line choke heavy duty) |
---|
Transmission Frame | RTU |
---|
With Safety Function Safe Speed Monitor (Ssm) | false |
---|
Relay Output Number | 2 |
---|
With Safety Function Safe Torque Off (Sto) | true |
---|
Data Format | 8 bits, configurable odd, even or no parity |
---|
Base Load Current At Low Overload | 2.8 A |
---|
Connector Type | 3 RJ45 |
---|
Pollution Degree | 2 EN/IEC 61800-5-1 |
---|
Analogue Output Number | 2 |
---|
Physical Interface | 2-wire RS 485 |
---|
Analogue Output Type | software-configurable voltage AQ1 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1 0...20 mA 500 Ohm 10 bits |
---|
Minimum Switching Current | relay output R1B 5 mA 24 V DC || relay output R2C 5 mA 24 V DC |
---|
Discrete Input Logic | 16 preset speeds |
---|
Continuous Output Current | 2.2 A 4 kHz heavy duty || 2.8 A 4 kHz normal duty |
---|
With Safety Function Safe Programmable Logic | false |
---|
Brake Chopper Integrated | true |
---|
Output Voltage | <= power supply voltage |
---|
Nominal Switching Frequency | 4 kHz |
---|
Braking To Standstill | by DC injection |
---|
Discrete Input Type | PTI safe torque off 0-30 kHz, 24 V DC 30 V) || DI1...DI5 discrete input, 24 V DC 30 V)3.5 kOhm |
---|
Protection Type | thermal protection motor || safe torque off motor || motor phase loss motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent drive || output overcurrent between motor phase and earth drive || output overcurrent between motor phases drive || short-circuit between motor phase and earth drive || short-circuit between motor phases drive || motor phase loss drive || DC Bus overvoltage drive || line supply overvoltage drive || line supply undervoltage drive || input supply loss drive || exceeding limit speed drive || break on the control circuit drive |
---|
Discrete Output Type | programmable output DQ1, DQ2 30 V DC 100 mA |
---|
With Safety Function Safely Limited Speed (Sls) | true |
---|
Synchronous Motor Control Profile | permanent magnet motor || reluctance motor |
---|
Electrical Connection | screw terminal 1.5...4 mm² line side || screw terminal 4...6 mm² DC bus || screw terminal 1.5...4 mm² motor || screw terminal 0.2...2.5 mm² control |
---|
Maximum Switching Current | relay output R1C resistive, cos phi = 1 3 A 250 V AC || relay output R1C resistive, cos phi = 1 3 A 30 V DC || relay output R1C inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1C inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2C resistive, cos phi = 1 5 A 250 V AC || relay output R2C resistive, cos phi = 1 5 A 30 V DC || relay output R2C inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R2C inductive, cos phi = 0.4 7 ms 2 A 30 V DC |
---|
Asynchronous Motor Control Profile | constant torque standard || variable torque standard || optimized torque mode |
---|
Product Certifications | UL || CSA || TÜV || EAC || CTick |
---|
Pollution Degree | 2 |
---|
Electromagnetic Compatibility | electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6 |
---|
Ambient Air Temperature For Operation | -15-50 °C without derating vertical position) || 50-60 °C with derating factor vertical position) |
---|
Volume Of Cooling Air | 18.0 m3/h |
---|
Marking | CE |
---|
Maximum Acceleration Under Vibrational Stress (During Operation) | 5 m/s² at 9...200 Hz |
---|
Noise Level | 52.7 dB |
---|
Ambient Air Temperature For Storage | -25-70 °C |
---|
Type Of Cooling | forced convection |
---|
Isolation | between power and control terminals |
---|
Maximum Deflection Under Vibratory Load (During Operation) | 1.5 mm at 2...9 Hz |
---|
Assembly Style | with heat sink |
---|
Operating Position | vertical +/- 10 degree |
---|
Ambient Air Transport Temperature | -40-70 °C |
---|
Standards | EN/IEC 61800-3 || EN/IEC 61800-5-1 || IEC 60721-3 || IEC 61508 || IEC 13849-1 || UL 618000-5-1 || UL 508C |
---|
Regulation Loop | adjustable PID regulator |
---|
Permitted Relative Humidity (During Operation) | class 3K5 according to EN 60721-3 |
---|
Operating Altitude | <= 9842.52 ft (3000 m) with current derating above 1000m |
---|
Overvoltage Category | class III |
---|
Environmental Class (During Operation) | class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3 |
---|
Maximum Acceleration Under Shock Impact (During Operation) | 70 m/s² at 22 ms |
---|