Control relay, TeSys K, 3 NO + 1 NC, lt or eq to 690V, 220 to 230VAC coil

Produttore:
Schneider Electric
Schneider electric

72330a0c592b62e64e3190d1181deb4e83083b2b medium
Prezzo (IVA esclusa)
€ 37.44
Codice Nuova Elva
CA2KN31M7
Codice produttore
CA2KN31M7
Disponibilità
Invia RdO

TeSys K control relay, 4 contacts (3NO + 1NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 220-230V 50/60Hz AC control circuit, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -25/+50°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium product (RoHS/REACh).

Specifications

CertificationsCB Scheme
Contact Configuration3 NO + 1 NC
Depth57 mm
Height58 mm
Net Weight0.18 kg
StandardCSA C22.2 No 60947-4-1
Storage Temperature-50-80 °C
Warranty Length18 months
Width45 mm

Specifications

[Ue] Rated Operational Voltage<= 690 V <= 400 Hz
Device Short NameCA2K
Control Circuit TypeAC 50/60 Hz
[Uc] Control Circuit Voltage220...230 V AC 50/60 Hz
Contactor Applicationcontrol circuit
Product Or Component Typecontrol relay
Product NameTeSys CAK
RangeTeSys
Pole Contact Composition3 NO + 1 NC
Utilisation CategoryAC-15 || DC-13

Contractual warranty

Warranty18 months

Complementary

Minimum Switching Current5 mA
Associated Fuse Rating10 A gG IEC 60947 || 10 A gG VDE 0660
Net Weight0.18 kg
Inrush Power In Va30-30 VA 20 °C)
Connections - Terminalsscrew clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible with cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-1.5 mm²flexible with cable end || screw clamp terminals 2 0.34-1.5 mm²flexible without cable end
Minimum Switching Voltage17 V
Maximum Operating Rate10000 cyc/h
Tightening Torque1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals Philips No 2 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
Mechanical Durability10 Mcycles
Hold-In Power Consumption In Va4.5-4.5 VA 20 °C)
Operating Time10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing || 15...25 ms coil de-energisation and NC closing || 5...15 ms coil energisation and NC opening
Height58 mm
Width45 mm
Depth57 mm
[Ui] Rated Insulation Voltage690 V IEC 60947 || 750 V VDE 0110 group C || 690 V BS 5424 || 600 V CSA C22.2 No 14
Heat Dissipation1.3-1.3 W
Control Circuit Voltage Limitsdrop-out 0.2...0.75 Uc 50 °C) || operational 0.8...1.15 Uc 50 °C)
Non Overlap Distance0.5 mm
[Ith] Conventional Free Air Thermal Current10 A 50 °C
Mounting Supportplate || rail
Immunity To Microbreaks2 ms
Insulation Resistance> 10 MOhm
Irms Rated Making Capacity110 A IEC 60947

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1503003EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP1503003EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Product CertificationsCB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Mechanical Robustnessvibrations contactor open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || shocks contactor open10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed15 Gn for 11 ms IEC 60068-2-27
Ambient Air Temperature For Operation-25-50 °C
StandardsEN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Flame RetardanceV1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage-50-80 °C
Protective TreatmentTC IEC 60068
Ip Degree Of ProtectionIP2X
Operating Altitude6561.68 ft (2000 m) without derating

Documentazione


Spesso acquistati assieme


Altri articoli da Schneider Electric

Richiedi un preventivo