TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 24V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).

Specifications

CertificationsCB Scheme
Contact Configuration3 NO + 2 NC
Depth93 mm
Height77 mm
Net Weight0.58 kg
StandardCSA C22.2 No 60947-5-1
Storage Temperature-60-80 °C
Warranty Length18 months
Width45 mm

Specifications

Contactor Applicationcontrol circuit
Product Or Component Typecontrol relay
Product NameTeSys CAD
RangeTeSys || TeSys Deca
Device Short NameCAD

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
[Uc] Control Circuit Voltage24 V DC
Hold-In Power Consumption In W5.4-5.4 W 20 °C
Insulation Resistance> 10 MOhm
Irms Rated Making Capacity140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Associated Fuse Rating10 A gG IEC 60947-5-1
Net Weight0.58 kg
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Connections - Terminalsscrew clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 1 1-4 mm²solid without cable end || screw clamp terminals 2 1-4 mm²solid without cable end
Pole Contact Composition3 NO + 2 NC
Time Constant28 ms
Minimum Switching Current5 mA
Utilisation CategoryDC-13 || AC-15 || AC-14
Minimum Switching Voltage17 V
Maximum Operating Rate180 cyc/mn
Tightening Torque1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2
Inrush Power In W5.4-5.4 W 20 °C)
Mechanical Durability30 Mcycles
Operating Time53...72 ms coil energisation and NO closing || 16...24 ms coil de-energisation and NO opening || 47...63 ms coil energisation and NC opening || 15...25 ms coil de-energisation and NC closing
Width45 mm
Depth93 mm
[Ui] Rated Insulation Voltage600 V UL || 600 V CSA || 690 V IEC 60947-5-1
Mechanical Robustnessshocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
[Icw] Rated Short-Time Withstand Current100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
[Ue] Rated Operational Voltage<= 690 V AC 25...400 Hz
Height77 mm
[Ith] Conventional Free Air Thermal Current10 A 60 °C
Control Circuit Voltage Limits0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Mounting Supportrail || plate
Control Circuit TypeDC standard

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110230EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Circularity ProfileENVEOLI1102030EN

Environment

Product CertificationsCB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Ambient Air Temperature For Operation-40-60 °C || 60-70 °C with derating
StandardsEN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Ambient Air Temperature For Storage-60-80 °C
Protective TreatmentTH IEC 60068
Ip Degree Of ProtectionIP2X front face VDE 0106
Operating Altitude0...9842.52 ft (0...3000 m)