TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 220 V AC standard coil
- Produttore:
- Schneider Electric
TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 220V 50/60Hz AC control circuit, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
Specifications
Certifications | CB Scheme |
---|---|
Contact Configuration | 3 NO + 2 NC |
Depth | 84 mm |
Height | 77 mm |
Net Weight | 0.58 kg |
Standard | CSA C22.2 No 60947-5-1 |
Storage Temperature | -60-80 °C |
Warranty Length | 18 months |
Width | 45 mm |
Specifications | |
Contactor Application | control circuit |
Product Or Component Type | control relay |
Product Name | TeSys CAD |
Range | TeSys || TeSys Deca |
Device Short Name | CAD |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Non-Overlap Time | 1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact |
[Uc] Control Circuit Voltage | 220 V AC 50/60 Hz |
Insulation Resistance | > 10 MOhm |
Irms Rated Making Capacity | 140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1 |
Associated Fuse Rating | 10 A gG IEC 60947-5-1 |
Net Weight | 0.58 kg |
[Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
Inrush Power In Va | 70-70 VA 50 Hz 20 °C) |
Connections - Terminals | screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 1 1-4 mm²solid without cable end || screw clamp terminals 2 1-4 mm²solid without cable end |
Pole Contact Composition | 3 NO + 2 NC |
Utilisation Category | DC-13 || AC-14 || AC-15 |
Minimum Switching Current | 5 mA |
Minimum Switching Voltage | 17 V |
Maximum Operating Rate | 180 cyc/mn |
Tightening Torque | 1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2 |
Mechanical Durability | 30 Mcycles |
Hold-In Power Consumption In Va | 8-8 VA 50 Hz 20 °C) |
Operating Time | 12...22 ms coil energisation and NO closing || 4...12 ms coil de-energisation and NO opening || 4...19 ms coil energisation and NC opening || 6...17 ms coil de-energisation and NC closing |
Width | 45 mm |
Depth | 84 mm |
[Ui] Rated Insulation Voltage | 600 V UL || 600 V CSA || 690 V IEC 60947-5-1 |
[Icw] Rated Short-Time Withstand Current | 100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms |
Mechanical Robustness | shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6 |
[Ue] Rated Operational Voltage | <= 690 V AC 25...400 Hz |
Height | 77 mm |
[Ith] Conventional Free Air Thermal Current | 10 A 60 °C |
Control Circuit Voltage Limits | 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz |
Mounting Support | plate || rail |
Control Circuit Type | AC 50/60 Hz |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP110230EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Circularity Profile | ENVEOLI1102030EN |
Environment | |
Product Certifications | CB Scheme || CCC || UL || CSA || EAC || CE || UKCA |
Ambient Air Temperature For Operation | -40-60 °C || 60-70 °C with derating |
Standards | EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1 |
Ambient Air Temperature For Storage | -60-80 °C |
Protective Treatment | TH IEC 60068 |
Ip Degree Of Protection | IP2X front face VDE 0106 |
Operating Altitude | 0...9842.52 ft (0...3000 m) |