TeSys Deca Manual Starter and Protector, magnetic circuit protector, rotary handle, 6.3 A, screw clamp terminals

Produttore:
Schneider Electric
Schneider electric

D541878315e003d43e797439a061cb2dfbdfdea0 medium
Prezzo (IVA esclusa)
€ 85.82
Codice Nuova Elva
GV2L10
Codice produttore
GV2L10
Disponibilità
Invia RdO

TeSys GV motor circuit breaker, 3 poles (3P), 6.3A/690V, for 3-phase motor applications 2.2kW@400V. It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by rotary handle guaranteed for 100 000 cycles AC-3. To complete motor protection, use in association with a thermal overload relay LRD010 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsBV
ColorGray
Depth97 mm
Height89 mm
Line Rated Current6.3 A
Net Weight0.33 kg
StandardCSA C22.2 No 60947-4-1
Storage Temperature-40-80 °C
Trip Point78-78 A
Warranty Length18 months
Width45 mm

Specifications

Product Or Component Typemotor circuit breaker
Product NameTeSys GV2 || TeSys Deca
RangeTeSys Deca
Device Applicationmotor protection
Device Short NameGV2L
Trip Unit Technologymagnetic

Contractual warranty

Warranty18 months

Complementary

Line Rated Current6.3 A
Net Weight0.33 kg
Fixing Mode35 mm symmetrical DIN rail clipped || panel screwed with 2 x M4 screws)
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947-2
[Ics] Rated Service Short-Circuit Breaking Capacity100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 690 V AC 50/60 Hz IEC 60947-2
Control Typerotary handle
Power Dissipation Per Pole1.8 W
Electrical Durability100000 cycles AC-3 415 V In
[Ui] Rated Insulation Voltage690 V AC 50/60 Hz IEC 60947-2
Breaking Capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolationyes IEC 60947-1 § 7-1-6
[Ue] Rated Operational Voltage690 V AC 50/60 Hz IEC 60947-2
Tightening Torque1.7 N.m screw clamp terminal
Mechanical Durability100000 cycles
Poles Description3P
Colordark grey
Width45 mm
Depth97 mm
Network Frequency50/60 Hz IEC 60947-2
Height89 mm
Rated Dutycontinuous IEC 60947-4-1
Network TypeAC
Magnetic Tripping Current78-78 A
[Ith] Conventional Free Air Thermal Current6.3 A IEC 60947-4-1
Motor Power Kw2.2-2.2 kW 400/415 V AC 50/60 Hz || 3-3 kW 500 V AC 50/60 Hz || 4-4 kW 690 V AC 50/60 Hz
Utilisation Categorycategory A IEC 60947-2 || AC-3 IEC 60947-4-1

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Eu Rohs DirectiveCompliant

Environment

Product CertificationsCCC || UL || CSA || EAC || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA || IECEE CB Scheme
Fire Resistance960 °C IEC 60695-2-11
Ik Degree Of ProtectionIK04
Mechanical Robustnessshocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Ambient Air Temperature For Operation-20-60 °C
StandardsEN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Climatic WithstandIACS E10
Ambient Air Temperature For Storage-40-80 °C
Ip Degree Of ProtectionIP20 IEC 60529
Operating Altitude6561.68 ft (2000 m)

Documentazione


Spesso acquistati assieme


Altri articoli da Schneider Electric

Richiedi un preventivo