Circuit breaker, PowerPacT J, 200A, 3 pole, 600VAC, 18kA, lugs, thermal magnetic, 80%
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 4186.80
- Codice Nuova Elva
- JGL36200
- Codice produttore
- JGL36200
- Disponibilità
- Invia RdO
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 200A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
Specifications
Certifications | CSA |
---|---|
Depth | 86 mm |
Height | 191 mm |
Line Rated Current | 200-200 A |
Mounting Type | Unit Mount Lug) |
Net Weight | 2.4 kg |
Standard | CSA |
Storage Temperature | -50-85 °C |
Strip Length | 25 mm |
Trip Point | 2000-2000 A |
Warranty Length | 18 months |
Width | 104 mm |
Specifications | |
Product Or Component Type | circuit breaker |
Product Name | PowerPact J |
Range | PowerPact |
Device Application | distribution |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Mounting Mode | unit mount lug) |
Breaking Capacity Code | G |
Magnetic Tripping Current | 2000-2000 A |
Local Signalling | switched off (OFF) 1 trip indicator green) |
Number Of Slots | 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in) |
Electrical Connection | lugs line || lugs load |
Mounting Height | 4.5 in |
Net Weight | 2.4 kg |
[Uimp] Rated Impulse Withstand Voltage | 8 kV IEC 60947-2 |
Magnetic Hold Current | 1000 A |
Control Type | toggle |
Network Frequency | 50/60 Hz |
Circuit Breaker Application | HACR rated |
Wire Stripping Length | 25 mm |
Utilisation Category | category A |
Line Rated Current | 200-200 A |
Long Time Pick-Up Adjustment Range | 0.25...1 x In |
Continuous Current Rating | 80 % |
Breaking Capacity | 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489 |
[Ui] Rated Insulation Voltage | 750 V IEC 60947-2 |
Suitability For Isolation | yes IEC 60947-2 |
Communication Interface | Modbus || Ethernet |
Terminal Identifier | AL250JD |
Poles Description | 3P |
Protection Type | overload protection || short-circuit protection |
Awg Gauge | AWG 3/0...350 kcmil aluminium/copper terminals |
Width | 104 mm |
Depth | 86 mm |
Phase Connection | ABC |
[Ics] Rated Service Breaking Capacity | 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2 |
Trip Unit Technology | thermal-magnetic |
Height | 191 mm |
[Ue] Rated Operational Voltage | 600 V AC 50/60 Hz IEC 60947-3 |
Tightening Torque | 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil) |
Mounting Support | lug |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP2206031EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Circularity Profile | ENVEOLI2206031EN |
Environment | |
Ambient Air Temperature For Operation | -2-70 °C |
Standards | UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2 |
Product Certifications | UL || CSA || NOM |
Ip Degree Of Protection | front cover IP40 |
Pollution Degree | 3 IEC 60947-1 |
Ambient Air Temperature For Storage | -50-85 °C |
Quality Labels | CE |
Operating Altitude | < 6561.68 ft (2000 m) without derating || 5000 m with derating |