Auxiliary contact block, TeSys Deca, 1NO, front mounting, screw clamp terminals
- Produttore:
- Schneider Electric
LADN10 is a Schneider Electric add-on auxiliary contact block for TeSys D and TeSys F contactors. Front mounting block, it provides 1NO instantaneous contact rated up to 10A 690V AC. LADN10 is a Schneider Electric add-on auxiliary contact block for TeSys D and TeSys F contactors. It provides 1NO instantaneous contact rated up to 10A 690V AC. Easy to mount on front by clip-on, it procures high reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Add-on block with 1NO auxiliary contact, with instantaneous operation. High electrical durability , several millions of operating cycles in AC-14/AC-15/DC-13 according conditions. Mounting by clip-on on front of all TeSys D and TeSys F contactors.
Specifications
Certifications | CB |
---|---|
Color | Gray |
Contact Configuration | 1 NO |
Depth | 35 mm |
Height | 48 mm |
Net Weight | 0.02 kg |
Standard | CSA C22.2 No 60947-5-1 |
Storage Temperature | -60-80 °C |
Warranty Length | 18 months |
Width | 13 mm |
Specifications | |
Product Certifications | CB || UL || CSA || CCC || EAC || UKCA |
Pole Contact Composition | 1 NO |
[Ui] Rated Insulation Voltage | 690 V IEC 60947-5-1 || 600 V UL || 600 V CSA |
[Ie] Rated Operational Current | 6 A120 V AC-15 || 1.04 A690 V AC-15 || 0.55 A125 V DC-13 || 0.1 A600 V DC-13 |
Auxiliary Contacts Operation | instantaneous |
Device Short Name | LADN |
[Ith] Conventional Free Air Thermal Current | 10 A 60 °C |
Standards | EN/IEC 60947-5-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.5 |
[Ue] Rated Operational Voltage | 690 V AC 25...400 Hz |
Range Compatibility | TeSys Deca LC1D80/95 3P || TeSys Deca LC1D80 4P || TeSys Deca LC1D40008 || TeSys Deca LC1D65008 || TeSys F LC1F || TeSys Deca LC1D115 |
Product Or Component Type | auxiliary contact block |
Product Name | TeSys Deca |
Range | TeSys || TeSys Deca |
Mounting Location | front |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Non-Overlap Time | 1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact |
Minimum Switching Voltage | 17 V |
Tightening Torque | 1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2 |
Mechanical Durability | 30 Mcycles |
Color | dark grey |
Width | 13 mm |
Depth | 35 mm |
Permissible Short-Time Rating | 100 A 60 °C 1 s || 120 A 60 °C 500 ms || 140 A 60 °C 100 ms |
Minimum Switching Current | 5 mA |
Height | 48 mm |
Protection Type | gG fuse 10 A |
Insulation Resistance | > 10 MOhm |
Irms Rated Making Capacity | 140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1 |
Net Weight | 0.02 kg |
Connections - Terminals | screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²rigid without cable end || screw clamp terminals 2 1-4 mm²rigid without cable end |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP110807EN_V2 |
Sustainable Offer Status | Green Premium product |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
Reach Free Of Svhc | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Environment | |
Ambient Air Temperature For Operation | -5-60 °C |
Ip Degree Of Protection | IP20 conforming to IEC 60529 |
Ambient Air Temperature For Storage | -60-80 °C |
Environmental Characteristic | normal environment |
Protective Treatment | TH IEC 60068 |
Operating Altitude | 9842.52 ft (3000 m) |