Time delay auxiliary contact block, TeSys Deca, 1NO + 1NC, off delay 10-180s, front, screw clamp terminals

Produttore:
Schneider Electric
Schneider electric

F56ba06cd9e120b6fed9d659f61b148b6f4d7f76 medium
Prezzo (IVA esclusa)
€ 83.43
Codice Nuova Elva
LADR4
Codice produttore
LADR4
Disponibilità
Tempo di consegna standard: 7 giorni

TeSys D time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 10-180s, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).

Specifications

CertificationsCCC
ColorGray
Contact Configuration1 NO + 1 NC
Depth61 mm
Height48 mm
StandardGB/T 14048.5
Storage Temperature-60-80 °C
Warranty Length18 months
Width44 mm

Specifications

Product CertificationsIECEE CB Scheme || UL || CSA || CCC || EAC || UKCA
Mounting Locationfront
Pole Contact Composition1 NO + 1 NC
[Ui] Rated Insulation Voltage690 V IEC 60947-5-1 || 600 V UL 60947-5-1 || 600 V CSA C22.2 No 60947-5-1
[Ie] Rated Operational Current6 A120 V AC-15 || 1.04 A690 V AC-15 || 0.55 A125 V DC-13 || 0.1 A600 V DC-13
Time Delay Range10...180 s
Auxiliary Contacts Operationtime delay
[Ith] Conventional Free Air Thermal Current10 A 60 °C
StandardsGB/T 14048.5
Timer Typeoff delay
[Ue] Rated Operational Voltage690 V AC 25...400 Hz
Range CompatibilityTeSys D CAD || TeSys D LC1D || TeSys F LC1F || TeSys F CR1F || TeSys Deca CAD || TeSys Deca LC1D
Product Or Component Typetime delay auxiliary contact block
Product NameTeSys Deca
RangeTeSys || TeSys Deca

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
Tightening Torque1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2
Mechanical Durability5 Mcycles
Colordark grey
Width44 mm
Depth61 mm
Permissible Short-Time Rating100 A 60 °C 1 s || 120 A 60 °C 500 ms || 140 A 60 °C 100 ms
Minimum Switching Current5 mA
Height48 mm
Protection TypegG fuse 10 A
Insulation Resistance> 10 MOhm
Irms Rated Making Capacity140 A <= 690 V AC IEC 60947-5-1 || 250 A <= 690 V DC IEC 60947-5-1
Connections - Terminalsscrew clamp terminals 1 1-2.5 mm²flexible with cable end || screw clamp terminals 1 1-2.5 mm²flexible without cable end || screw clamp terminals 1 1-2.5 mm²rigid || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible without cable end || screw clamp terminals 2 1-2.5 mm²rigid || screw clamp terminals
Minimum Switching Voltage17 V

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110702
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: Cancer - www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Ambient Air Temperature For Operation-40-70 °C
Ip Degree Of ProtectionIP20 conforming to IEC 60529
Ambient Air Temperature For Storage-60-80 °C
Environmental Characteristicnormal environment
Protective TreatmentTH IEC 60068
Operating Altitude9842.52 ft (3000 m)