TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 110A resistive load rating. Contactor is supplied with a 220 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.78 inches wide and 5.51 inches deep. It weighs 4.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Specifications

CertificationsCB
Contact Configuration2 NO + 2 NC
Depth140 mm
Height127 mm
Impedance0.8 MOhm - Ith 125 A 50 Hz Power Circuit
Net Weight1.84 kg
StandardCSA C22.2 No 60947-4-1
Warranty Length18 months
Width96 mm

Specifications

[Uc] Control Circuit Voltage220 V AC 50/60 Hz
Device Short NameLC1D
[Ue] Rated Operational Voltagepower circuit <= 690 V AC 25...400 Hz
Range Of ProductTeSys Deca
Contactor Applicationresistive load
Product Or Component Typecontactor
RangeTeSys
Utilisation CategoryAC-1
[Ie] Rated Operational Current125 A 60 °C) <= 440 V AC AC-1 power circuit
Poles Description4P

Contractual warranty

Warranty18 months

Complementary

Power Dissipation Per Pole12.5 W AC-1
Rated Breaking Capacity1100 A 440 V power circuit IEC 60947
Irms Rated Making Capacity1100 A 440 V power circuit IEC 60947
Associated Fuse Rating200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage8 kV IEC 60947
Inrush Power In Va245-245 VA 60 Hz 0.75 20 °C) || 245-245 VA 50 Hz 0.75 20 °C)
Pole Contact Composition2 NO + 2 NC
Connections - Terminalscontrol circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² flexible without cable end || control circuit screw clamp terminals 2 1-4 mm² flexible without cable end || control circuit screw clamp terminals 1 1-4 mm² solid without cable end || control circuit screw clamp terminals 2 1-4 mm² solid without cable end || power circuit connector 1 4-50 mm² flexible without cable end || power circuit connector 2 4-25 mm² flexible without cable end || power circuit connector 1 4-50 mm² flexible with cable end || power circuit connector 2 4-16 mm² flexible with cable end || power circuit connector 1 4-50 mm² solid without cable end || power circuit connector 2 4-25 mm² solid without cable end
Coil Technologywithout built-in suppressor module
Operating Time20...35 ms closing || 6...20 ms opening
Maximum Operating Rate3600 cyc/h 60 °C
Average Impedance0.8 mOhm - Ith 125 A 50 Hz power circuit
Tightening Torquecontrol circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability0.8 Mcycles 125 A AC-1 <= 440 V
Mechanical Durability4 Mcycles
Compatibility CodeLC1D
Hold-In Power Consumption In Va26-26 VA 60 Hz 0.3 20 °C) || 26-26 VA 50 Hz 0.3 20 °C)
Overvoltage CategoryIII
[Ui] Rated Insulation Voltagepower circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current640 A 40 °C - 10 s power circuit || 990 A 40 °C - 1 s power circuit || 135 A 40 °C - 10 min power circuit || 320 A 40 °C - 1 min power circuit
Heat Dissipation6-10 W 50/60 Hz
Protective Coverwithout
[Ith] Conventional Free Air Thermal Current125 A 60 °C power circuit
Control Circuit Voltage Limits0.85...1.1 Uc -40-55 °C operational AC 60 Hz || 0.3...0.6 Uc -40-55 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55 °C operational AC 50 Hz
Mounting Supportplate || rail
Contact CompatibilityM1
Control Circuit TypeAC 50/60 Hz
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree3

Offer Sustainability

Rohs Exemption InformationYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110205EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes

Environment

Product CertificationsUL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width96 mm
Depth140 mm
Permissible Ambient Air Temperature Around The Device-40-60 °C || 60-70 °C with derating
Height127 mm
StandardsEN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Climatic WithstandIACS E10 exposure to damp heat
Net Weight1.84 kg
Flame RetardanceV1 conforming to UL 94
Protective TreatmentTHIEC 60068-2-30
Ip Degree Of ProtectionIP20 front face IEC 60529
Mechanical Robustnessvibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)