contactor, TeSys F, 3P(3NO), AC-3, <=440V 185A with coil LX9, 24...600V AC 40/400Hz, LX4, 24...460V DC, LXE, 100...250V AC 50/60Hz or 100…380V DC

Produttore:
Schneider Electric
Schneider electric

B8e2731a9727376070c0fa6591e167c26b44bd9a medium
Codice Nuova Elva
LC1F185
Codice produttore
LC1F185
Disponibilità
Invia RdO

TeSys F contactor, 3 poles (3NO), 185A/690V AC-3, for motor applications up to 90kW@400V. Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsABS
Contact Configuration3 NO
Depth181 mm
Height174 mm
Impedance0.33 MOhm - Ith 275 A 50 Hz
Net Weight5.45 kg
StandardEN 60947-1
Storage Temperature-60-80 °C
Warranty Length18 months
Width168.5 mm

Specifications

[Ue] Rated Operational Voltage<= 690 V AC 50/60 Hz || <= 460 V DC
Motor Power Kw100 kW 415 V AC 50/60 Hz AC-3) || 100 kW 440 V AC 50/60 Hz AC-3) || 110 kW 500 V AC 50/60 Hz AC-3) || 90 kW 380...400 V AC 50/60 Hz AC-3) || 55 kW 220...240 V AC 50/60 Hz AC-3) || 110 kW 660...690 V AC 50/60 Hz AC-3) || 33 kW 400 V AC 50/60 Hz AC-4)
Device Short NameLC1F
Contactor Applicationresistive load || motor control
Product Or Component Typecontactor
Product NameTeSys F
RangeTeSys
Pole Contact Composition3 NO
[Ie] Rated Operational Current275 A 40 °C) <= 440 V AC-1 || 185 A 55 °C) <= 440 V AC-3
Utilisation CategoryAC-3 || AC-4 || AC-1
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Product CertificationsABS || LROS (Lloyds register of shipping) || RINA || CSA || CB || UL || BV || RMRoS || DNV || UKCA
Irms Rated Making Capacity1850 A IEC 60947-4-1
Associated Fuse Rating200 A aM <= 440 V || 315 A gG <= 440 V
[Uimp] Rated Impulse Withstand Voltage8 kV
Inrush Power In Va950-1180 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil || 737-902 VA (at 20 °C)with LX4 coil || 280-310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil || 270-320 VA (at 20 °C)with LXE coil
Connections - Terminalspower circuit bar 2 25 x 3 mm || power circuit lugs-ring terminals 1 150-150 mm² || power circuit connector 1 150-150 mm² || power circuit bolted connection || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm² || control circuit screw clamp terminals 2 1-4 mm² || control circuit screw clamp terminals 1.0 0.2-2.5 mm²flexible without cable end || control circuit screw clamp terminals 1.0 0.25-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1.0 0.2-2.5 mm²solid without cable end
Operating Time35 ms closing with LX9 coil || 130 ms opening with LX9 coil || 30...40 ms closing with LX4 coil || 30...50 ms opening with LX4 coil || 40...80 ms closing with LXE coil || 6...54 ms opening with LXE coil
Tightening Torquepower circuit 18 N.m || control circuit 1.2 N.m || control circuit 0.6 N.m
Mechanical Durability10 Mcycles
Compatibility CodeLC1F
Hold-In Power Consumption In Va8.9-10.9 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil || 4.13-5.07 VA (at 20 °C)with LX4 coil || 4.5-7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil || 2.5-4.0 VA (at 20 °C)with LXE coil
Power Dissipation Per Pole25 W AC-1 || 12 W AC-3
Overvoltage CategoryIII
[Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current1500 A 40 °C - 10 s || 920 A 40 °C - 30 s || 740 A 40 °C - 1 min || 500 A 40 °C - 3 min || 400 A 40 °C - 10 min
Heat Dissipation8-9.8 W || 2.2-2.5 W
Average Impedance0.33 mOhm - Ith 275 A 50 Hz
Control Circuit Voltage Limitsoperational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil || drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil || operational: 0.85...1.1 Uc DC with LX4 coil || drop-out: 0.15...0.2 Uc DC with LX4 coil || operational: 85...275 V AC 50/60 Hz with LXE coil || drop-out: 0...60 V AC 50/60 Hz with LXE coil || operational: 85...418 V DC with LXE coil || drop-out: 0...45 V DC with LXE coil
[Ith] Conventional Free Air Thermal Current275 A 40 °C
StandardsIEC 60947-4-1 || EN 60947-1 || JIS C8201-4-1 || EN 60947-4-1 || IEC 60947-1
[Uc] Control Circuit Voltage24...575 V AC 40...400 Hz with LX9 coil || 24...460 V DC with LX4 coil || 100...250 V AC 50/60 Hz with LXE coil || 100...380 V DC with LXE coil
Mounting Supportplate
Rated Breaking Capacity1480 A IEC 60947-4-1

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI100418
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP080208EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.

Environment

Mechanical Robustnessvibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed5 Gn, 5...300 Hz || shocks contactor open7 Gn for 1/2 sine wave (11 ms) || shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Depth181 mm
Permissible Ambient Air Temperature Around The Device-40-70 °C
Ambient Air Temperature For Operation-5-55 °C
Height174 mm
Net Weight5.45 kg
Ambient Air Temperature For Storage-60-80 °C
Protective TreatmentTH
Ip Degree Of ProtectionIP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Width168.5 mm

Documentazione


Spesso acquistati assieme


Articoli correlati


Richiedi un preventivo