TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 48 V AC coil
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 297.45
- Codice Nuova Elva
- LC2D32E7
- Codice produttore
- LC2D32E7
- Disponibilità
- Tempo di consegna standard: 8 giorni
LC2D32E7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 32A AC-3 15kW@400V, it includes a 48V 50/60Hz AC coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D32E7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 15kW@400V. It includes a 48V 50/60Hz AC coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 48V AC coil that can be supplied at 50Hz or 60Hz. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 2 million cycles at 32A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.
Specifications
Certifications | BV |
---|---|
Contact Configuration | 1 NO + 1 NC |
Depth | 92 mm |
Height | 85 mm |
Impedance | 2 MOhm - Ith 50 A 50 Hz Power Circuit |
Net Weight | 0.797 kg |
Standard | CSA C22.2 No 14 |
Storage Temperature | -60-80 °C |
Warranty Length | 18 months |
Width | 90 mm |
Specifications | |
Product Certifications | UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA |
Control Circuit Type | AC 50/60 Hz |
Standards | CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1 |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Contactor Application | resistive load || motor control |
Rated Breaking Capacity | 550 A 440 V power circuit IEC 60947 |
Product Or Component Type | reversing contactor |
Irms Rated Making Capacity | 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947 |
Product Name | TeSys Deca |
Associated Fuse Rating | 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit |
[Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
Interlocking Type | mechanical |
Connections - Terminals | control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit screw clamp terminals 1 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 1 1-10 mm²flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm²solid || power circuit screw clamp terminals 2 2.5-10 mm²solid |
Range | TeSys || TeSys Deca |
Pole Contact Composition | 3 NO |
Device Presentation | preassembled with reversing power busbar |
Utilisation Category | AC-1 || AC-3 |
[Ie] Rated Operational Current | 32 A 60 °C) <= 440 V AC AC-3 power circuit || 50 A 60 °C) <= 440 V AC AC-1 power circuit |
Maximum Operating Rate | 3600 cyc/h 60 °C |
Tightening Torque | control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2 |
Electrical Durability | 1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V |
Mechanical Durability | 15 Mcycles |
[Uc] Control Circuit Voltage | 48 V AC 50/60 Hz |
Poles Description | 3P |
Operating Time | 12...22 ms closing || 4...19 ms opening |
Overvoltage Category | III |
Motor Power Kw | 7.5 kW 220...230 V AC 50 Hz || 15 kW 380...400 V AC 50 Hz || 15 kW 415...440 V AC 50 Hz || 18.5 kW 500 V AC 50 Hz || 18.5 kW 660...690 V AC 50 Hz |
Maximum Horse Power Rating | 2 hp 115 V at AC 60 Hz for 1 phase || 5 hp 230/240 V at AC 60 Hz for 1 phase || 7.5 hp 200/208 V at AC 60 Hz for 3 phase || 10 hp 230/240 V at AC 60 Hz for 3 phase || 20 hp 460/480 V at AC 60 Hz for 3 phase || 30 hp 575/600 V at AC 60 Hz for 3 phase |
[Ui] Rated Insulation Voltage | power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL |
Device Short Name | LC2D |
[Icw] Rated Short-Time Withstand Current | 60 A 40 °C - 10 min power circuit || 138 A 40 °C - 1 min power circuit || 260 A 40 °C - 10 s power circuit || 430 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit |
Protective Cover | with |
[Ue] Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC |
Power Dissipation Per Pole | 2 W AC-3 || 5 W AC-1 |
Average Impedance | 2 mOhm - Ith 50 A 50 Hz power circuit |
Auxiliary Contact Composition | 1 NO + 1 NC |
[Ith] Conventional Free Air Thermal Current | 10 A 60 °C signalling circuit || 50 A 60 °C power circuit |
Mounting Support | plate || rail |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact |
Hold-In Power Consumption In Va | 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C) |
Heat Dissipation | 2-3 W 50/60 Hz |
Minimum Switching Current | 5 mA signalling circuit |
Control Circuit Voltage Limits | 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz |
Insulation Resistance | > 10 MOhm signalling circuit |
Inrush Power In Va | 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C) |
Coil Technology | without built-in suppressor module |
Minimum Switching Voltage | 17 V signalling circuit |
Signalling Circuit Frequency | 25...400 Hz |
Auxiliary Contacts Type | mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1 |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Circularity Profile | ENVEOLI1102029EN |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP110229EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Environment | |
Mechanical Robustness | vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms |
Ip Degree Of Protection | IP20 front face IEC 60529 |
Operating Altitude | 0...9842.52 ft (0...3000 m) |
Fire Resistance | 850 °C IEC 60695-2-1 |
Width | 90 mm |
Depth | 92 mm |
Ambient Air Temperature For Operation | -40-60 °C || 60-70 °C with derating |
Height | 85 mm |
Climatic Withstand | IACS E10 || IEC 60947-1 Annex Q category D |
Pollution Degree | 3 |
Net Weight | 0.797 kg |
Flame Retardance | V1 conforming to UL 94 |
Ambient Air Temperature For Storage | -60-80 °C |
Protective Treatment | TH IEC 60068-2-30 |