Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 6A, 1 NO aux, 24VDC coil
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 41.31
- Codice Nuova Elva
- LP1K0610BD
- Codice produttore
- LP1K0610BD
- Disponibilità
- Invia RdO
LP1K0610BD is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 24V DC coil and 1NO auxiliary contact allowing easy integration to all control systems. LP1K0610BD is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 2.2kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it can be easily integrated into all control systems thanks to its 24V DC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Ready for connection to all control systems thanks to a 24V DC control voltage and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
Specifications
Certifications | CB Scheme |
---|---|
Contact Configuration | 1 NO |
Depth | 57 mm |
Impedance | 3 MOhm - Ith 20 A 50 Hz Power Circuit |
Net Weight | 0.225 kg |
Standard | CSA C22.2 No 60947-4-1 |
Storage Temperature | -50-80 °C |
Warranty Length | 18 months |
Specifications | |
Auxiliary Contact Composition | 1 NO |
Device Short Name | LP1K |
Range Of Product | TeSys K |
Contactor Application | motor control |
Product Or Component Type | contactor |
Range | TeSys |
Pole Contact Composition | 3 NO |
Utilisation Category | AC-4 || AC-3 || AC-3e |
[Ie] Rated Operational Current | 6 A<= 440 V AC AC-3 power circuit || 6 A<= 440 V AC AC-3e power circuit |
Poles Description | 3P |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Minimum Switching Current | 5 mA signalling circuit |
Rated Breaking Capacity | 110 A 415 V IEC 60947 || 110 A 440 V IEC 60947 || 80 A 500 V IEC 60947 || 110 A 220...230 V IEC 60947 || 110 A 380...400 V IEC 60947 || 70 A 660...690 V IEC 60947 |
Irms Rated Making Capacity | 110 A AC power circuit NF C 63-110 || 110 A AC power circuit IEC 60947 || 110 A AC signalling circuit IEC 60947 |
Associated Fuse Rating | 25 A gG <= 440 V power circuit || 25 A aM power circuit || 10 A gG signalling circuit IEC 60947 || 10 A gG signalling circuit VDE 0660 |
Net Weight | 0.225 kg |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Flame Retardance | V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102 |
Minimum Switching Voltage | 17 V signalling circuit |
Maximum Operating Rate | 3600 cyc/h |
Inrush Power In W | 3-3 W 20 °C) |
Mechanical Durability | 10 Mcycles |
[Ue] Rated Operational Voltage | power circuit 690 V AC 50/60 Hz || signalling circuit <= 690 V AC 50/60 Hz |
Auxiliary Contacts Type | instantaneous 1 NO |
Operating Time | 30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening |
Tightening Torque | 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2 |
Overvoltage Category | III |
Depth | 57 mm |
[Ui] Rated Insulation Voltage | power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-5-1 || signalling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || signalling circuit 600 V CSA C22.2 No 14 |
Average Impedance | 3 mOhm - Ith 20 A 50 Hz power circuit |
Control Circuit Voltage Limits | operational 0.8...1.15 Uc 50 °C) || drop-out 0.1...0.75 Uc 50 °C) |
[Ith] Conventional Free Air Thermal Current | 20 A 50 °C power circuit || 10 A 50 °C signalling circuit |
Mounting Support | rail || plate |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Hold-In Power Consumption In W | 3-3 W 20 °C |
Insulation Resistance | > 10 MOhm signalling circuit |
Offer Sustainability | |
Rohs Exemption Information | Yes |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Circularity Profile | ENVEOLI1503003EN |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1503003EN |
Sustainable Offer Status | Green Premium product |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Environment | |
Product Certifications | CB Scheme || CCC || UL || CSA || EAC || CE || UKCA |
Standards | EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 |
Ambient Air Temperature For Storage | -50-80 °C |
Operating Altitude | 6561.68 ft (2000 m) without derating |