Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 6A, 1 NO aux, 24VDC coil

Produttore:
Schneider Electric
Schneider electric

954f48d080b1428160ca55d16675e10e5f248c7d medium
Prezzo (IVA esclusa)
€ 41.31
Codice Nuova Elva
LP1K0610BD
Codice produttore
LP1K0610BD
Disponibilità
Invia RdO

LP1K0610BD is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 24V DC coil and 1NO auxiliary contact allowing easy integration to all control systems. LP1K0610BD is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 2.2kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it can be easily integrated into all control systems thanks to its 24V DC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Ready for connection to all control systems thanks to a 24V DC control voltage and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).

Specifications

CertificationsCB Scheme
Contact Configuration1 NO
Depth57 mm
Impedance3 MOhm - Ith 20 A 50 Hz Power Circuit
Net Weight0.225 kg
StandardCSA C22.2 No 60947-4-1
Storage Temperature-50-80 °C
Warranty Length18 months

Specifications

Auxiliary Contact Composition1 NO
Device Short NameLP1K
Range Of ProductTeSys K
Contactor Applicationmotor control
Product Or Component Typecontactor
RangeTeSys
Pole Contact Composition3 NO
Utilisation CategoryAC-4 || AC-3 || AC-3e
[Ie] Rated Operational Current6 A<= 440 V AC AC-3 power circuit || 6 A<= 440 V AC AC-3e power circuit
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Minimum Switching Current5 mA signalling circuit
Rated Breaking Capacity110 A 415 V IEC 60947 || 110 A 440 V IEC 60947 || 80 A 500 V IEC 60947 || 110 A 220...230 V IEC 60947 || 110 A 380...400 V IEC 60947 || 70 A 660...690 V IEC 60947
Irms Rated Making Capacity110 A AC power circuit NF C 63-110 || 110 A AC power circuit IEC 60947 || 110 A AC signalling circuit IEC 60947
Associated Fuse Rating25 A gG <= 440 V power circuit || 25 A aM power circuit || 10 A gG signalling circuit IEC 60947 || 10 A gG signalling circuit VDE 0660
Net Weight0.225 kg
[Uimp] Rated Impulse Withstand Voltage8 kV
Flame RetardanceV1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate3600 cyc/h
Inrush Power In W3-3 W 20 °C)
Mechanical Durability10 Mcycles
[Ue] Rated Operational Voltagepower circuit 690 V AC 50/60 Hz || signalling circuit <= 690 V AC 50/60 Hz
Auxiliary Contacts Typeinstantaneous 1 NO
Operating Time30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening
Tightening Torque0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Overvoltage CategoryIII
Depth57 mm
[Ui] Rated Insulation Voltagepower circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-5-1 || signalling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || signalling circuit 600 V CSA C22.2 No 14
Average Impedance3 mOhm - Ith 20 A 50 Hz power circuit
Control Circuit Voltage Limitsoperational 0.8...1.15 Uc 50 °C) || drop-out 0.1...0.75 Uc 50 °C)
[Ith] Conventional Free Air Thermal Current20 A 50 °C power circuit || 10 A 50 °C signalling circuit
Mounting Supportrail || plate
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Hold-In Power Consumption In W3-3 W 20 °C
Insulation Resistance> 10 MOhm signalling circuit

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1503003EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP1503003EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Product CertificationsCB Scheme || CCC || UL || CSA || EAC || CE || UKCA
StandardsEN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Ambient Air Temperature For Storage-50-80 °C
Operating Altitude6561.68 ft (2000 m) without derating

Documentazione


Spesso acquistati assieme


Altri articoli da Schneider Electric

Richiedi un preventivo