Reversing contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NO, 24VDC coil

Produttore:
Schneider Electric
Schneider electric

C60f4632ce665ffce09dd8a4826902b8e030cc21 medium
Codice Nuova Elva
LP2K0910BD3
Codice produttore
LP2K0910BD3
Disponibilità
Invia RdO

TeSys K reversing contactor, 3 poles (3NO), for motor control applications up to 6A/690V AC-3 (2.2kW@400V). It provides 24V DC coil with transient suppressor module, 2NO built-in auxiliary contacts, connection by screw clamp terminals. For operating rates until 600 cycles/hour in AC-3 and environments until 50°C, it procures reliability and durability to standard applications. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsCB Scheme
Contact Configuration1 NO
Depth57 mm
Height58 mm
Impedance3 MOhm - Ith 20 A 50 Hz Power Circuit
Net Weight0.48 kg
StandardCSA C22.2 No 60947-4-1
Storage Temperature-50-80 °C
Warranty Length18 months
Width90 mm

Specifications

Product CertificationsCB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Control Circuit TypeDC standard
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Applicationmotor control || resistive load
Rated Breaking Capacity110 A 415 V IEC 60947 || 110 A 440 V IEC 60947 || 80 A 500 V IEC 60947 || 110 A 220...230 V IEC 60947 || 110 A 380...400 V IEC 60947 || 70 A 660...690 V IEC 60947
Product Or Component Typereversing contactor
Irms Rated Making Capacity110 A AC power circuit NF C 63-110 || 110 A AC power circuit IEC 60947 || 110 A AC signalling circuit IEC 60947
Product NameTeSys K
Associated Fuse Rating25 A gG <= 440 V power circuit || 25 A aM power circuit || 10 A gG signalling circuit IEC 60947 || 10 A gG signalling circuit VDE 0660
[Uimp] Rated Impulse Withstand Voltage8 kV
Connections - Terminalsscrew clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end
Interlocking Typemechanical
RangeTeSys
Pole Contact Composition3 NO
Device Presentationpreassembled with reversing power busbar
Utilisation CategoryAC-4 || AC-1 || AC-3 || AC-3e
[Ie] Rated Operational Current20 A 50 °C) <= 440 V AC AC-1 power circuit || 16 A 70 °C) 690 V AC AC-1 power circuit || 9 A<= 440 V AC AC-3 power circuit || 9 A<= 440 V AC AC-3e power circuit
Maximum Operating Rate3600 cyc/h
Electrical Durability0.18 Mcycles 20 A AC-1 <= 440 V || 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V
Mechanical Durability5 Mcycles
Poles Description3P
Operating Time30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening
[Uc] Control Circuit Voltage24 V DC
Tightening Torque0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Overvoltage CategoryIII
Motor Power Kw2.2 kW 220...230 V AC 50/60 Hz || 4 kW 380...415 V AC 50/60 Hz || 4 kW 440 V AC 50/60 Hz || 4 kW 480 V AC 50/60 Hz || 4 kW 500...600 V AC 50/60 Hz || 4 kW 660...690 V AC 50/60 Hz
[Ui] Rated Insulation Voltagepower circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-5-1 || signalling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || signalling circuit 600 V CSA C22.2 No 14
Device Applicationcontrol
Device Short NameLP2K
[Icw] Rated Short-Time Withstand Current90 A 50 °C - 1 s power circuit || 85 A 50 °C - 5 s power circuit || 80 A 50 °C - 10 s power circuit || 60 A 50 °C - 30 s power circuit || 45 A 50 °C - 1 min power circuit || 40 A 50 °C - 3 min power circuit || 80 A - 1 s signalling circuit || 90 A - 500 ms signalling circuit || 110 A - 100 ms signalling circuit || 20 A 50 °C - >= 15 min power circuit
[Ue] Rated Operational Voltagepower circuit 690 V AC 50/60 Hz || signalling circuit <= 690 V AC 50/60 Hz
Average Impedance3 mOhm - Ith 20 A 50 Hz power circuit
Auxiliary Contact Composition1 NO
[Ith] Conventional Free Air Thermal Current20 A 50 °C power circuit || 10 A 50 °C signalling circuit
StandardsEN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Mounting Supportplate || rail

Contractual warranty

Warranty18 months

Complementary

Minimum Switching Current5 mA signalling circuit
Heat Dissipation3-3 W
Control Circuit Voltage Limitsoperational 0.8...1.15 Uc 50 °C) || drop-out 0.1...0.75 Uc 50 °C)
Non Overlap Distance0.5 mm
Hold-In Power Consumption In W3-3 W 20 °C
Insulation Resistance> 10 MOhm signalling circuit
Coil Technologybuilt-in bidirectional peak limiting diode suppressor
Minimum Switching Voltage17 V signalling circuit
Inrush Power In W3-3 W 20 °C)
Auxiliary Contacts Typeinstantaneous 1 NO

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1503003EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP1503003EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Mechanical Robustnessshocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 || shocks contactor opened, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Y axis6 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on X axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis10 Gn for 11 ms IEC 60068-2-27
Width90 mm
Depth57 mm
Ambient Air Temperature For Operation-25-50 °C
Height58 mm
Net Weight0.48 kg
Flame RetardanceV1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage-50-80 °C
Protective TreatmentTC IEC 60068 || TC DIN 50016
Ip Degree Of ProtectionIP20 VDE 0106
Operating Altitude6561.68 ft (2000 m) without derating

Documentazione


Spesso acquistati assieme


Altri articoli da Schneider Electric

Richiedi un preventivo