TeSys LRF - electronic thermal overload relay - 60...100 A - class 10

Produttore:
Schneider Electric
Schneider electric

9e0e1672d451948e8348e995db0e4fe7e9ae5d07 medium
Codice Nuova Elva
LR9F5367
Codice produttore
LR9F5367
Disponibilità
Invia RdO

TeSys LR9F electronic overload relay, thermal setting range 60-100A, class 10, for protection of motors 37-45kW@400V. to be mounted directly below a TeSys F 3-pole contactor LC1 F115, F150, F185, use of a support mounting plate LA7F901 is recommended (to be ordered separately). Motor protection includes thermal overload of 1-phase and 3-phase motors, phase failure, phase unbalance, prolonged starting times, stalled rotor conditions. On the front of the relay, it provides a thermal adjustement dial, buttons for test, stop & reset, a trip indicator, trip auxiliary contacts 1NO+1NC. Multi standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).

Specifications

CertificationsCSA
Current5 mA
Depth123.5 mm
Height96 mm
Net Weight0.9 kg
StandardEN 60947-4-1
Storage Temperature-40-85 °C
Warranty Length18 months
Width115 mm

Specifications

Network TypeAC
Thermal Protection Adjustment Range60-100 A
Relay Applicationmotor protection
Product Or Component Typeelectronic thermal overload relay
Product NameTeSys LRF
Thermal Overload Classclass 10 IEC 60947-4
RangeTeSys
Product CompatibilityLC1F115...LC1F185
Device Short NameLR9F

Contractual warranty

Warranty18 months

Complementary

Network Frequency50/60 Hz
Net Weight0.9 kg
[Uimp] Rated Impulse Withstand Voltage8 kV IEC 60947-1
Maximum Voltage Drop<2.5 V closed state
Connections - Terminalscontrol circuit screw clamp terminals 1 0.75-2.5 mm² flexible - with cable end || control circuit screw clamp terminals 1 0.75-2.5 mm² solid || control circuit screw clamp terminals 1 0.75-4 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1.5 mm² flexible - with cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1 mm² solid || power circuit lugs-ring terminals M8
[Ui] Rated Insulation Voltagepower circuit 1000 V AC IEC 60947-4
Contacts Type And Composition1 NO + 1 NC
Surge Withstand4 kV IEC 61000-4-5
Tripping Threshold1.12 +/- 0.06 In tripping IEC 60947-4-1
Mounting Supportdirect on contactor || plate
Control Typedial White full-load current adjustment || test button Red || push-button Red reset || push-button stop
Current Consumption<= 5 mA no-load
Local Signallingtrip indicator
Width115 mm
Depth123.5 mm
Temperature Compensation-20-70 °C
Height96 mm
[Ith] Conventional Free Air Thermal Current5 A control circuit
Tightening Torquecontrol circuit 1.2 N.m screw clamp terminals || power circuit 18 N.m screw clamp terminals
Resetmanual reset on front relay
Phase Failure Sensitivitytripping in 4 s +/- 20 % IEC 60947-4-1
[Ue] Rated Operational Voltage1000 V AC 50/60 Hz power circuit VDE 0110 group C
Switching Capacity In Ma0...150 mA

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI100406
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP080207EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.

Environment

Product CertificationsUL || CSA || UKCA
Operating Altitude<= 6561.68 ft (2000 m) without derating
Fire Resistance850 °C IEC 60695-2-1
Mechanical Robustnessshocks13 Gn for 11 ms IEC 60068-2-7 || vibrations 5...300 Hz2 GN IEC 60068-2-6
StandardsIEC 60255-8 || VDE 0660 || IEC 60255-17 || IEC 60947-4-1 || EN 60947-4-1
Ambient Air Temperature For Operation-20-55 °C IEC 60255-8
Electromagnetic Compatibilityresistance to electrostatic discharge 6 kV in indirect mode IEC 61000-4-2 || resistance to electrostatic discharge 8 kV in air IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test 10 V/m IEC 61000-4-3 || fast transients immunity test 2 kV IEC 61000-4-4
Dielectric Strength6 kV 50 Hz IEC 255-5
Ip Degree Of ProtectionIP20 conforming to IEC 60529 || IP20 conforming to VDE 0106
Ambient Air Temperature For Storage-40-85 °C
Protective TreatmentTH