Reversing power base, TeSys Ultra, 3P, 12A/690V, coil 24VAC
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 167.22
- Codice Nuova Elva
- LU2B12B
- Codice produttore
- LU2B12B
- Disponibilità
- Tempo di consegna standard: 8 giorni
TeSys U standard reversing power base, 3 poles (3NO), rated 12A/690V, to be completed with a control unit LUC to form a TeSys U reversing starter controller, for 3-phase motor applications up to 5.5kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a "all in one" reversing starter controller with basic or advanced protection and control functions. It is equipped with a reverser module LU2MB0B to be supplied with 24V AC, auxiliary signaling contacts (1NO+1NC), a control terminal block, blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Specifications
Certifications | ASEFA |
---|---|
Contact Configuration | 1 NO + 1 NC |
Depth | 126 mm |
Height | 224 mm |
Net Weight | 1.27 kg |
Standard | CSA C22.2 No 60947-4-1, With Phase Barrier |
Storage Temperature | -40-85 °C |
Warranty Length | 18 months |
Width | 45 mm |
Specifications | |
[Ics] Rated Service Breaking Capacity | 50 kA 230 V || 50 kA 440 V || 10 kA 500 V || 4 kA 690 V |
[Ie] Rated Operational Current | 12 A <= 440 V || 12 A 500 V || 9 A 690 V |
Suitability For Isolation | yes |
Product Compatibility | control unit LUC.X6B || control unit LUC.1XB || control unit LUC.05B || control unit LUC.12B |
Auxiliary Contacts Type | linked contacts 1 NO + 1 NC) IEC 60947-4-1 || mirror contact 1 NC) IEC 60947-1 |
Poles Description | 3P |
Control Circuit Voltage Limits | 14.5 V AC drop-out || 20...26.5 V AC in operation |
Network Frequency | 40...60 Hz |
Device Application | motor control || motor protection |
Device Short Name | LU2B |
[Ue] Rated Operational Voltage | 690 V AC power circuit |
Auxiliary Contact Composition | 1 NO + 1 NC |
[Uc] Control Circuit Voltage | 24 V AC 50/60 Hz |
Product Or Component Type | reversing power base |
[Ith] Conventional Free Air Thermal Current | 12 A |
Product Name | TeSys Ultra |
Range | TeSys |
Utilisation Category | AC-43 || AC-44 || AC-41 |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Product Certifications | CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine |
Standards | EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier |
[Ui] Rated Insulation Voltage | 690 V IEC 60947-6-2 3) || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1 |
Typical Current Consumption | 2360 mA 24 V AC I maximum while closing |
Mechanical Durability | 15 Mcycles |
Compatibility Code | LU2B |
Operating Time | 150 ms with change of direction power circuit || 35 ms opening control circuit || 70 ms closing control circuit || 75 ms without change of direction power circuit |
Width | 45 mm |
Tightening Torque | control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips no 1 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm || power circuit 1.9-2.5 N.m pozidriv No 2 6 mm |
Safe Separation Of Circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N |
Depth | 126 mm |
Height | 224 mm |
Heat Dissipation | 2-2 W control circuit with LUCA, LUCB, LUCC, LUCD || 1.7-1.7 W control circuit with LUCM |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Maximum Operating Rate | 3600 cyc/h |
Connections - Terminals | control circuit screw clamp terminals 1 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² rigid || control circuit screw clamp terminals 2 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 2 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 2 0.75-1.5 mm² rigid || power circuit screw clamp terminals 1 1-10 mm² rigid || power circuit screw clamp terminals 1 1-6 mm² flexible with cable end || power circuit screw clamp terminals 1 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 2 1-6 mm² flexible with cable end || power circuit screw clamp terminals 2 1-6 mm² rigid || power circuit screw clamp terminals 2 1.5-6 mm² flexible without cable end |
Net Weight | 1.27 kg |
Fixing Mode | clipped DIN rail) || screw-fixed plate) |
[Uimp] Rated Impulse Withstand Voltage | 6 kVIEC 60947-6-2 |
Inrush Restraint Duration | 25 ms AC 50/60 Hz |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Eu Rohs Directive | Compliant |
Environment | |
Ambient Air Temperature For Operation | -25-60 °C with LUCM || -25-70 °C with LUCA, LUCB, LUCC, LUCD |
Resistance To Electrostatic Discharge | 8 kV 3 in open air IEC 61000-4-2 || 8 kV 4 on contact IEC 61000-4-2 |
Ip Degree Of Protection | IP20 IEC 60947-1 front panel and wired terminals) || IP20 IEC 60947-1 other faces) || IP40 IEC 60947-1 front panel outside connection zone) |
Fire Resistance | 960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12 |
Immunity To Radioelectric Fields | 10 V IEC 61000-4-6 |
Resistance To Fast Transients | 2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4 |
Operating Altitude | 6561.68 ft (2000 m) |
Resistance To Radiated Fields | 10 V/m 3 IEC 61000-4-3 |
Non-Dissipating Shock Wave | 1 kV serial mode IEC 60947-6-2 || 2 kV common mode IEC 60947-6-2 |
Shock Resistance | 10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27 |
Immunity To Microbreaks | 3 ms control circuit |
Immunity To Voltage Dips | 70 % / 500 ms IEC 61000-4-11 |
Vibration Resistance | 2 gn 5-300 Hz) power poles open IEC 60068-2-27 || 4 gn 5-300 Hz) power poles closed IEC 60068-2-27 |
Ambient Air Temperature For Storage | -40-85 °C |
Protective Treatment | TH IEC 60068 |