Ultra compact starter, TeSys Hybrid, Safe Torque Off, 3P, 500VAC, 3kW at 400V, 24VDC,
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 196.65
- Codice Nuova Elva
- LZ7H6X5BD
- Codice produttore
- LZ7H6X5BD
- Disponibilità
- Invia RdO
TeSys H ultra compact direct safety starter, 3 poles, 6.5A/500V AC-53, for control and protection of 3-phase motors up to 3kW@400V (3HP@480V). The hybrid technology used for power contacts procures ultra compactness (22.5mm width) as well as an extended electrical durability up to 30 million cycles AC-53. It provides control for one direction of rotation, an adjustable motor current 1.5-6.5A, class 10A thermal overload protection with auto/manual/remote reset, phase loss and phase unbalanced protection, stall and jam motor protection. To be supplied with 24V DC, it provides logic inputs for ON/OFF motor running and remote reset after thermal tripping, 1C/O contact relay for fault indication, LED status on front face for indication of tripping and motor running. With an integrated Safe Torq Off (STO) function with SIL3 level according IEC61508-1 and PLe level according ISO13849-1, it can be integrated to safety chain applications. DIN rail mounting, screw terminals for control and power, it can be used for ambient temperatures from -25 to 70°C, without derating until 30°C. Multi standards certified (IEC, UL, CCC), Green Premium compliant (RoHS/REACh).
Specifications
Contact Configuration | 1 C |
---|---|
Current | 40 mA |
Depth | 114.5 mm |
Height | 99 mm |
Mounting Type | Clips |
Net Weight | 212 g |
Standard | IEC 60947-4-2 |
Storage Temperature | -40-80 °C |
Width | 22.5 mm |
Specifications | |
[Uc] Control Circuit Voltage | 24 V DC |
[Ie] Rated Operational Current | 6.5 A 500 V AC-53A || 9 A 500 V AC-51 || 5 A 500 V AC-53A mounting side by side || 7 A 500 V AC-51 mounting side by side |
Poles Description | 3P |
Safety Reliability Data | MTTFd = 517 years stop function || SFF = 99 % stop function || SFF = 99 % motor protection || MTTFd = 447 years motor protection || PFHd = 2.40E-9 1/h stop function |
Maximum Horse Power Rating | 1 hp 200 V AC || 1.5 hp 230 V AC || 3 hp 460 V AC |
Device Short Name | LZ7H |
Safety Level | SIL 3 IEC 61508-1 stop function || PL = e ISO 13849-1 stop function || SIL 2 IEC 61508-1 motor protection |
[Ue] Rated Operational Voltage | 500 V AC |
Thermal Protection Adjustment Range | 1.5-9 A |
Product Or Component Type | ultra-compact starter |
Product Name | TeSys Hybrid |
Thermal Overload Class | class 10A IEC 60947-4-2 |
Motor Power Kw | 1.5 kW 220 V AC 0.65 || 1.5 kW 230 V AC 0.65 || 2.2 kW 380 V AC 0.65 || 3 kW 400 V AC 0.65 || 3 kW 415 V AC 0.65 || 3 kW 440 V AC 0.65 || 3 kW 500 V AC 0.65 |
Range | TeSys |
Motor Starter Type | direct on line |
Complementary | |
Height | 99 mm |
[Ui] Rated Insulation Voltage | 500 V AC 50/60 Hz |
Mounting Mode | by clips |
Maximum Operating Rate | 120 cyc/mn AC-51 50 % || 6 cyc/mn AC-53A 50 % |
Auxiliary Contact Composition | 1 C/O fault signalling |
Control Circuit Voltage Limits | 19.2...30 V DC |
Certifications | ATEX as associated device for motor protection in zones 1 and 21 || CE || cULus |
Width | 22.5 mm |
Tightening Torque | 0.5-0.6 N.m flat Ø 2.5 mm 3 mm |
Depth | 114.5 mm |
Electrical Durability | 30 Mcycles |
Reset | manual || electrical reset |
Standards | UL 60947-4-1 || IEC 60947-4-2 |
Mounting Support | DIN rail |
Pollution Degree | 2 |
Net Weight | 212 g |
[Uimp] Rated Impulse Withstand Voltage | 6 kV |
Connections - Terminals | screw clamp terminals 1 0.2-2.5 mm² rigid || screw clamp terminals 1 0.25-2.5 mm² flexible - with cable end || screw clamp terminals 1 0.2-2.5 mm² flexible - without cable end |
Current Consumption | <= 40 mA 24 V DC |
Offer Sustainability | |
Rohs Exemption Information | Yes |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI1509013EN |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1509013EN |
Sustainable Offer Status | Green Premium product |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Environment | |
Ambient Air Temperature For Operation | -25-30 °C without derating || 30-70 °C with derating |
Ambient Air Temperature For Storage | -40-80 °C |
Protective Treatment | TC |
Ip Degree Of Protection | IP20 |