Miniature circuit breaker (MCB), Multi9 C60H-DC, 2P, 16A, C curve, 5kA (UL1077), 6kA (IEC/EN 60947-2)

Produttore:
Schneider Electric
Schneider%20electric

9ebac80f7b0500899ca0368273c4813f2614d642 medium
Prezzo (IVA esclusa)
€ 90.09
Codice Nuova Elva
M9U21216
Codice produttore
M9U21216
Disponibilità
Invia RdO

This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 2P circuit breaker with 2 protected poles, 16A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 20kA at 220VDC conforming to EN/IEC 60947-2 standard and 20kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.

Specifications

CertificationsCCC
ColorGray
Depth73 mm
Height81 mm
Line Rated Current25 °C
Mounting TypeClip-On
Net Weight0.128 kg
StandardEN/IEC 60947-2
Storage Temperature-40-85 °C
Strip Length14 mm
Width36 mm

Specifications

Line Rated Current16 A 25 °C EN/IEC 60947-2
RangeMulti9
Breaking Capacity20 kA Icu 220 V DC EN/IEC 60947-2 || 10 kA Icu 440 V DC EN/IEC 60947-2 || 6 kA Icu 500 V DC EN/IEC 60947-2 || 5 kA AIR 12...500 V DC UL 1077 || 20 kA Icu 220 V DC GB 14048.2 || 10 kA Icu 440 V DC GB 14048.2 || 6 kA Icu 500 V DC GB 14048.2
Suitability For Isolationyes EN/IEC 60947-2
Poles Description2P
Device Applicationdistribution
Device Short NameC60H-DC
Trip Unit Technologythermal-magnetic
Curve CodeC
Number Of Protected Poles2
Network TypeDC
StandardsEN/IEC 60947-2 || GB 14048.2 || UL 1077
Product CertificationsIEC || CCC || UR
Product Or Component Typeminiature circuit-breaker
Product NameMulti9 C60H-DC
Utilisation Categorycategory A EN/IEC 60947-2

Complementary

[Ics] Rated Service Breaking Capacity7.5 kA 75 % EN/IEC 60947-2 - 440 V DC || 4.5 kA 75 % EN/IEC 60947-2 - 500 V DC || 15 kA 75 % EN/IEC 60947-2 - 220 V DC || 7.5 kA 75 % GB 14048.2 - 440 V DC || 4.5 kA 75 % GB 14048.2 - 500 V DC || 15 kA 75 % GB 14048.2 - 220 V DC
Connections - Terminalstunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - rigid stranded || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 6) - flexible || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 6) - flexible with ferrule || tunnel type terminal top or bottom) - 2 1-10 mm² AWG 18...AWG 8) - rigid stranded || tunnel type terminal top or bottom) - 2 1-10 mm² AWG 18...AWG 8) - flexible || tunnel type terminal top or bottom) - 2 1-10 mm² AWG 18...AWG 8) - flexible with ferrule || tunnel type terminal top or bottom) - 3 1-1 mm² AWG 18) - flexible stranded
[Ui] Rated Insulation Voltage500 V DC EN/IEC 60947-2
Mounting Modeclip-on
Electrical Durability3000 cycles 250 V DC L/R = 2 ms || 6000 cycles 250 V DC
Mechanical Durability20000 cycles
Local SignallingON/OFF indication
[Uimp] Rated Impulse Withstand Voltage6 kVEN/IEC 60947-2
ColorGray
Width36 mm
Provision For Padlockingpadlockable
Height81 mm
Depth73 mm
Tightening Torque2.5-2.5 N.m top or bottom
Magnetic Tripping Limit7...10 x In DC
[Ue] Rated Operational Voltage220 V DC || 440 V DC || 500 V DC
Contact Position Indicatoryes
Earth-Leakage Protectionwithout
Mounting SupportDIN rail
9 Mm Pitches4
Net Weight0.128 kg
Wire Stripping Length14 mm top or bottom
Control Typetoggle

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs DirectiveCompliant

Environment

Ambient Air Temperature For Operation-25-70 °C
Tropicalisation2 IEC 60068-2 || 2 GB 14048.2
Ip Degree Of ProtectionIP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree3 EN/IEC 60947-2
Ambient Air Temperature For Storage-40-85 °C
Relative Humidity95-95 % 55-55 °C
Heat Dissipation5-5 W 440 V - 16 A

Documentazione


Altri articoli da Schneider Electric

Richiedi un preventivo