Modular liquid level control relay, Harmony, 5A, 2CO, 24...240V AC DC

Produttore:
Schneider Electric
Schneider electric

B3b256f908497dfd3ff6164b1edcfda18b3b5822 medium
Prezzo (IVA esclusa)
€ 76.03
Codice Nuova Elva
RM35LM33MW
Codice produttore
RM35LM33MW
Disponibilità
Invia RdO

This Harmony RM35-LM relay allows monitoring of level control in 3-phase networks. This modular multi function 3-phase liquid level control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0

Specifications

CertificationsC-tick
Housing MaterialPlastic
Operating Cycles360
StandardEN/IEC 60255-6
Storage Temperature-40-70 °C
Warranty Length18 months
Width35 mm

Specifications

Minimum Switching Current10 mA 5 V DC
Relay Typelevel control relay
Time Delay Typeadjustable 0.1...5 s, +/- 10 %
Relay Monitored Parametersdetection by resistive probes
Maximum Power Consumption In Va5 VA AC
Maximum Switching Current5 A AC/DC
Range Of ProductHarmony Control Relays
Measurement Range250 Ohm...1 MOhm
Switching Capacity In Va1250 VA
Product Or Component Typelevel control relay
Utilisation CategoryAC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
Relay NameRM35L
Contacts Type And Composition2 C/O

Contractual warranty

Warranty18 months

Complementary

[Us] Rated Supply Voltage24...240 V AC/DC 50/60 Hz +/- 10 %
MarkingCE : 73/23/EEC || CE : EMC 89/336/EEC
Operating Positionany position without derating
Sensitivity Scale0.25...5 kOhm LS (Low Sensitivity) || 5...100 kOhm St (Standard Sensitivity) || 50...1000 kOhm HS (High Sensitivity)
Maximum Switching Voltage250 V AC/DC
Connections - Terminalsscrew terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
[Ui] Rated Insulation Voltage250 V IEC 60664-1
Overvoltage CategoryIII IEC 60664-1
Supply Voltage Limits20.4-264 V AC/DC
Mounting Support35 mm symmetrical DIN rail conforming to EN/IEC 60715
Nominal Output Current5 A
Safety Reliability DataB10d = 170000 || MTTFd = 182.6 years
Local Signallingfor relay ON LED (yellow) || for power ON LED (green) || for timer ON LED (yellow)
Mechanical Durability30000000 cycles
Maximum Supply Current For Sensors1 mA
Housing Materialself-extinguishing plastic
Measurement Accuracy+/- 10 % of the full scale value || +/- 20 % for the HS range
Width35 mm
Tightening Torque0.6-1 N.m IEC 60947-1
Maximum Power Consumption In W1.5 W DC
Sensitivity Adjustment5-100 %
Electrical Durability100000 cycles
Control Circuit Voltage Limits15 % + 10 % Un
Run-Up Delay At Power-Up0.6 s
Repeat Accuracy+/- 2 % time delay
Cable Capacitance1 nF HS (High Sensitivity) probe cable || 2.2 nF St (Standard Sensitivity) probe cable || 4.7 nF LS (Low Sensitivity)
Insulation Resistance> 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 || > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 || > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
Measurement Error0.5 %/°C with temperature variation
Operating Rate<= 360 operations/hour full load
Output Contacts2 C/O
Reset Time1750 ms

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP1504008EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs RegulationX
Circularity ProfileENVEOLI1504008EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)

Environment

Product CertificationsCSA || GL || UL || C-tick || GOST
Relative Humidity95-95 % 55-55 °C IEC 60068-2-30
StandardsEN/IEC 60255-6
Dielectric Test Voltage2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1
Electromagnetic Compatibilityemission standard for industrial environments EN/IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 || immunity for industrial environments NF EN/IEC 61000-6-2
Immunity To Microbreaks100 ms DC || 90 ms AC
Ambient Air Temperature For Operation-20-50 °C
Ip Degree Of ProtectionIP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
Pollution Degree3 IEC 60664-1
Ambient Air Temperature For Storage-40-70 °C