TeSys Vario enclosed, emergency stop switch disconnector, 16A, IP55
- Produttore:
- Schneider Electric
VCFN20GE is a direct-on-line TeSys enclosed starter from Schneider Electric. Enclosure fitted with a yellow cover, red padlockable rotary handle, and a 3-pole VN20 switch body with 2 possible add-on module attachments. Rated The 16A 690V, it is used for main and emergency stop switching in motor applications up to 5.5kW@400V AC-23. Cabling through 2 cable glands on top and bottom, it provides IP55 protection. It conforms to IEC 60947-4-1, Green Premium compliant (RoHS/REACh).
Specifications
Depth | 106 mm |
---|---|
Height | 131 mm |
Net Weight | 0.422 kg |
Standard | IEC 60947-4-1 |
Warranty Length | 18 months |
Width | 82.5 mm |
Specifications | |
Rotary Handle Padlocking | 1 to 3 padlocks 4-8 mm |
Device Short Name | VCFN |
Handle Front Plate Colour | yellow |
Handle Colour | red |
Product Or Component Type | emergency stop switch disconnector |
Product Name | TeSys Mini-VARIO |
Performance Level | standard |
Range | TeSys |
Control Type | rotary handle |
Poles Description | 3P |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
[Ue] Rated Operational Voltage | 690 V AC |
Making Capacity | 200 A 400 V AC-21A || 200 A 400 V AC-22A || 200 A 400 V AC-23A |
[Icm] Rated Short-Circuit Making Capacity | 0.5 kA 400 V at Ipeak |
Electrical Durability | 30000 cycles DC-1...5 || 50000 cycles AC-21 |
Suitability For Isolation | yes |
[Ie] Rated Operational Current | 11 A AC-23A)400 V |
Mechanical Durability | 50000 cycles |
Fire Resistance | 960 °C IEC 60595-2-1 |
Width | 82.5 mm |
Tightening Torque | control circuit 0.7-0.7 N.m connector |
Depth | 106 mm |
Height | 131 mm |
Breaking Capacity | 200 A 400 V AC-21A) || 200 A 400 V AC-22A) || 200 A 400 V AC-23A) |
Rated Operational Power In W | 5.5 kW 400 V AC-23) || 4 kW 400 V AC-3) |
Rated Conditional Short-Circuit Current | 6 kA 400 V 20 A aM || 6 kA 400 V 20 A gG |
[Icw] Rated Short-Time Withstand Current | 140 A 400 V 1 s |
Intermittent Duty Class | 30 |
[Ithe] Conventional Enclosed Thermal Current | 16 A |
Marking | 0 - 1 |
Base Dimension | 60 x 60 mm |
Connections - Terminals | control circuit connector 4-4 mm² flexible with cable end || control circuit connector 4-4 mm² solid |
Net Weight | 0.422 kg |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Offer Sustainability | |
Rohs Exemption Information | Yes |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP111273EN |
Sustainable Offer Status | Green Premium product |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Environment | |
Ambient Air Temperature For Operation | -20-50 °C |
Standards | IEC 60947-4-1 |
Protective Treatment | TC |
Mechanical Robustness | vibrations 10...150 Hz 1 gn) IEC 60068-2-6 || shocks 11 ms 30 Gn) IEC 60068-2-27 |