Limit switch, XC Standard, XCKJ, thermoplastic plastic roller lever var. length, 1NC+1 NO, snap, M20

Produttore:
Schneider Electric
Schneider electric

B07aaa34933098b02da7c2333ead21e1fa745d7c medium
Prezzo (IVA esclusa)
€ 66.02
Codice Nuova Elva
XCKJ10541H29
Codice produttore
XCKJ10541H29
Disponibilità
Invia RdO

This XCKJ industrial format (EN 50041) limit switch has a thermoplastic variable length roller lever and a Zamak body. This limit switch has a robust Zamak body and head, a modular design allowing easier maintenance and a industrial CENELEC EN50041 form A format. It is IP66 and IK07 impact resistant, making it ideal for heavy duty use in harsh conditions. It is fixed on the machine by its body, and has a typical 5 million cycles electrical durability in DC-13 utilization category. It complies with CCC, EN/IEC 60947.-5-1, CSA C22.2 No.14, EN/IEC 60204-1, UL 508, BV, EAC standards. Compatible with the well distributed range of common XCK heads, allowing quick replacement in case of damage. Variable composition design allows late modifications on the switch, for example change of connection type or head.

Specifications

CertificationsCCC
Depth44 mm
Height77-77 mm
MaterialMetal
Net Weight0.485 kg
Number of Poles2
Number of Steps1
StandardCENELEC EN 50041
Storage Temperature-40-70 °C
Warranty Length18 months
Width40 mm

Specifications

Movement Of Operating Headrotary
Head Typerotary head
Type Of Approachlateral approach, 1 or 2 programmable direction
Series Namestandard format
Contacts Type And Composition1 NC + 1 NO
Body Typefixed
Contact Operationsnap action
Body Materialzamak
Device Short NameXCKJ
Number Of Poles2
Range Of ProductTelemecanique Limit switches XC Standard
Fixing Modeby the body
Type Of Operatorspring return roller lever thermoplastic variable length
Cable Entry1 entry tapped for M20 x 1.5 cable gland 7-13 mm
Product Or Component Typelimit switch
Head Materialzamak
Materialmetal

Contractual warranty

Warranty18 months

Complementary

Height77-77 mm
[Ui] Rated Insulation Voltage300 VUL 508 || 500 V 3)IEC 60947-1 || 300 VCSA C22.2 No 14
Electrical Durability5000000 cycles, DC-13, inductive, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, inductive, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, inductive, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Positive Openingwithout
Contacts Insulation FormZb
[Ie] Rated Operational Current3 A 240 V, AC-15, A300 EN/IEC 60947-5-1 appendix A || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 appendix A
Mechanical Durability30000000 cycles
Maximum Actuation Speed1.5 m/s
Width40 mm
Depth44 mm
Minimum Torque For Tripping0.25 N.m
Terminals Description Iso N°1(13-14)NO || (21-22)NC
Maximum Resistance Across Terminals25 MOhm IEC 60255-7 category 3
Short-Circuit Protection10 A cartridge fuse gG
Electrical Connectionscrew-clamp terminals 1 x 0.34...2 x 1.5 mm²
Number Of Steps1
[Ithe] Conventional Enclosed Thermal Current10 A
Net Weight0.485 kg
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60664 || 6 kV IEC 60947-1
Switch Actuationby 30° cam

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP110614EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)

Environment

Product CertificationsUL || CCC || CSA
Protective TreatmentTH
Ik Degree Of ProtectionIK07 EN 50102
Ambient Air Temperature For Operation-25-70 °C
StandardsUL 508 || CENELEC EN 50041 || IEC 60204-1 || IEC 60947-5-1 || EN 60947-5-1 || EN 60204-1 || CSA C22.2 No 14
Shock Resistance50 gn 11 ms IEC 60068-2-27
Vibration Resistance25 gn 10-500 Hz)IEC 60068-2-6
Ip Degree Of ProtectionIP66 conforming to IEC 60529
Ambient Air Temperature For Storage-40-70 °C
Overvoltage Categoryclass I IEC 61140 || class I NF C 20-030

Documentazione


Spesso acquistati assieme


Articoli correlati


Richiedi un preventivo