This XCKP compact format (CENELEC EN 50047) limit switch has a thermoplastic variable length roller lever and a plastic body. This limit switch has a double insulated thermoplastic body, a modular design allowing easier maintenance and a compact CENELEC EN50047 format. It is IP66 and IK04 impact resistant, making it ideal for heavy duty use in harsh conditions. It is fixed on the machine by its body, and has a typical 5 million cycles electrical durability in DC-13 utilization category. It complies with CCC, EN/IEC 60947.-5-1, CSA C22.2 No.14, EN/IEC 60204-1, UL 508 standards. Compatible with the well distributed range of common XCK heads, allowing quick replacement in case of damage. Variable composition design allows late modifications on the switch, for example change of connection type or head.

Specifications

CertificationsCCC
Depth30 mm
Height65-65 mm
MaterialPlastic
Net Weight0.145 kg
Number of Poles2
StandardCSA C22.2 No 14
Storage Temperature-40-70 °C
Warranty Length18 months
Width31 mm

Specifications

Movement Of Operating Headrotary
Type Of Approachlateral approach, 2 directions
Series Namestandard format
Contacts Type And Composition1 NC + 1 NO
Body Typefixed
Contact Operationsnap action
Body Materialplastic
Device Short NameXCKP
Number Of Poles2
Range Of ProductTelemecanique Limit switches XC Standard
Fixing Modeby the body
Type Of Operatorspring return roller lever thermoplastic variable length
Sensor Designcompact
Product Or Component Typelimit switch
Head Materialzamak
Materialplastic
Head Typerotary head

Contractual warranty

Warranty18 months

Complementary

Height65-65 mm
Electrical Durability5000000 cycles, DC-13, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Positive Openingwith
Contacts Insulation FormZb
Positive Opening Minimum Torque0.25 N.m
Mechanical Durability10000000 cycles
Maximum Actuation Speed1.5 m/s
Contact Code DesignationA300, AC-15 (Ue = 240 V), Ie = 3 A 10 A EN/IEC 60947-5-1 appendix A || Q300, DC-13 (Ue = 250 V), Ie = 0.27 A EN/IEC 60947-5-1 appendix A
Width31 mm
Depth30 mm
Minimum Torque For Tripping0.1 N.m
Terminals Description Iso N°1(21-22)NC || (13-14)NO
Repeat Accuracy0.1 mm on the tripping points with 1 million operating cycles
Maximum Resistance Across Terminals25 MOhm IEC 60255-7 category 3
Short-Circuit Protection10 A cartridge fuse gG
Electrical Connectionscrew-clamp terminals 1 x 0.34...2 x 1.5 mm²
Cable Entry1 entry tapped for M16 x 1.5 cable gland 4-8 mm
Net Weight0.145 kg
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60664 || 6 kV IEC 60947-1
Switch Actuationby 30° cam
[Ui] Rated Insulation Voltage300 VUL 508 || 500 V 3)IEC 60947-1 || 300 VCSA C22.2 No 14

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP110606EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity ProfileENVEOLI110603EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)

Environment

Product CertificationsCSA || UL || CCC
Protective TreatmentTC
Ik Degree Of ProtectionIK04 EN 50102
Ambient Air Temperature For Operation-25-70 °C
StandardsUL 508 || EN 60947-5-1 || IEC 60947-5-1 || IEC 60204-1 || EN 60204-1 || CSA C22.2 No 14
Shock Resistance50 gn 11 ms IEC 60068-2-27
Vibration Resistance25 gn 10-500 Hz)IEC 60068-2-6
Ip Degree Of ProtectionIP66 conforming to IEC 60529 || IP67 conforming to IEC 60529
Ambient Air Temperature For Storage-40-70 °C
Electrical Shock Protection Classclass II IEC 61140 || class II NF C 20-030

Documentazione


Spesso acquistati assieme


Altri articoli da Schneider Electric

Richiedi un preventivo