Coded magnetic switch, Telemecanique Safety switches XCS, XCSDMC, 2 NC, staggered, 10 m
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 72.68
- Codice Nuova Elva
- XCSDMC79010
- Codice produttore
- XCSDMC79010
- Disponibilità
- Invia RdO
This product is part of the XCS range, an offer of safety limit switches. The coded magnetic switch is an electrical switch that makes or breaks contact in the presence of a magnetic field. It has 2 normally closed, staggered contacts. It is a switch with a rated operational current of 100mA, rated operational voltage of 24V DC, a switching capacity of 0.1 to 100mA and maximum switching voltage of 100V DC. It is designed to operate in hazardous environments. It is furnished with a 10m pre-cabled (4 x 0.25mm²) for electrical connection. It supports lateral approach in 3 directions. It offers long electrical life with electrical durability of about 1.2 million operating cycles. It is an IP66 and IP67 rated product. The casing is made of thermoplastic PBT. Its dimensions are 16mm (Width) x 7mm (Depth) x 51mm (Height) and weighs 0.101kg. It is intended as far as safety is concerned all dangerous machines in all sectors are involved. Such as packaging, handling, robotics, machine tools, presses, automotive sector. This product is certified by BG, CSA, UL. It meets CSA C22.2 No 14, EN/IEC 60947-5-1, EN/IEC 60204-1, EN/ISO 12100, ISO 14119 and UL 508 standards. The coded magnetic switch offers protection of operators by stopping the machine when the actuator attached to the machine guard is withdrawn from the head of the switch. Safety switches for the protection of operators, by controlling the safe opening and interlocking of guards and covers in your installations.
Specifications
Cable Length | 10 m |
---|---|
Certifications | CSA |
Contact Material | Rhodium |
Depth | 7 mm |
Enclosure Material | Thermoplastic |
Height | 51 mm |
Material | Plastic |
Net Weight | 0.101 kg |
Number of Poles | 2 |
Operating Temperature | -25-85 °C |
Standard | CSA C22.2 No 14 |
Storage Temperature | -40-85 °C |
Warranty Length | 18 months |
Width | 16 mm |
Specifications | |
Range Of Product | Telemecanique Safety switches XCS |
Contact Operation | staggered |
Electrical Connection | pre-cabled |
Cable Composition | 4 x 0.25 mm² |
Approach Directions | 3 directions |
[Ui] Rated Insulation Voltage | 100 V DC |
Number Of Poles | 2 |
[Ue] Rated Operational Voltage | 24 V DC |
Cable Length | 10 m |
Product Or Component Type | coded magnetic switch |
Component Name | XCSDMC |
Material | plastic |
Design | rectangular, compact |
Size | 51 x 16 x 7 mm |
Contacts Type And Composition | 2 NC |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Maximum [Ie] Rated Operational Current | 100 mA |
Net Weight | 0.101 kg |
[Uimp] Rated Impulse Withstand Voltage | 2.5 kV EN/IEC 60947-5-1 |
Maximum Switching Voltage | 100 V DC |
[Sa] Assured Operating Distance | 5 mm |
Cable Material | PVC |
Breaking Capacity | 10 VA |
Safety Reliability Data | B10d = 50000000 value given for a life time of 20 years limited by mechanical or contact wear |
Enclosure Material | thermoplastic PBT |
Width | 16 mm |
Depth | 7 mm |
Height | 51 mm |
Electrical Durability | 1200000 cycles |
Safety Level | can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach SIL 3 with the appropriate monitoring system and correctly wired EN/IEC 61508 |
Switching Frequency | 150 Hz |
Short-Circuit Protection | 500 mA external cartridge fuse gG (gl) |
Switching Capacity In Ma | 0.1...100 mA |
[Sar] Assured Tripping Distance | 15 mm |
Contacts Material | rhodium |
Insulation Resistance | 1000 MOhm |
Resistance Across Terminals | 10 Ohm |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Environment | |
Product Certifications | UL || CSA |
Protective Treatment | TH |
Ambient Air Temperature For Operation | -25-85 °C |
Standards | EN/IEC 60204-1 || UL 508 || CSA C22.2 No 14 || EN/IEC 60947-5-1 || EN/ISO 12100 || ISO 14119 |
Shock Resistance | 30 gn 11 ms IEC 60068-2-27 |
Vibration Resistance | 10 gn 10-150 Hz)IEC 60068-2-6 |
Ip Degree Of Protection | IP66 conforming to IEC 60529 || IP67 conforming to IEC 60529 |
Ambient Air Temperature For Storage | -40-85 °C |
Electrical Shock Protection Class | class II EN/IEC 61140 |
Maximum Sensitivity To Magnetic Fields | 0.3 mT |