pressure switch XMLB 10 bar - adjustable scale 2 thresholds - 1 C/O
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 177.75
- Codice Nuova Elva
- XMLB010A2S11
- Codice produttore
- XMLB010A2S11
- Disponibilità
- Invia RdO
This XMLB electromechanical pressure switch has an adjustable differential for regulation of 2 thresholds and a zinc alloy body with a range scale window. This pressure switch is designed for regulation of pressure between 2 thresholds for air, fresh water and hydraulic oils at temperatures up to 70°C. It is fixed directly on tubage. It provides zinc alloy enclosure for robust performance. 5 million cycles mechanical durability for minimum required maintenance on your pressurized fluid circuits. It complies with CCC, EN/IEC 60947-5-1, CSA C22.2 No.14, LROS, UL 508, EAC, BV.
Specifications
Certifications | BV |
---|---|
Contact Material | Silver |
Depth | 75 mm |
Enclosure Material | Zinc Alloy |
Height | 113 mm |
Line Rated Current | 0.1 A |
Net Weight | 0.705 kg |
Standard | CE |
Storage Temperature | -40-70 °C |
Warranty Length | 18 months |
Width | 35 mm |
Specifications | |
Contacts Type And Composition | 1 C/O |
Adjustable Range Of Switching Point On Falling Pressure | 0.13-9.15 bar |
Materials In Contact With Fluid | zinc alloy || FPM, FKM |
Local Display | with |
Fluid Connection Type | G 1/4 (female) ISO 228 |
Pressure Sensor Size | 10 bar |
Controlled Fluid | air 0-70 °C) || fresh water 0-70 °C) || hydraulic oil 0-70 °C) |
Awg Gauge | AWG 20...AWG 14 |
Scale Type | adjustable differential |
Electrical Circuit Type | control circuit |
Pressure Sensor Type | electromechanical pressure sensor |
Enclosure Material | zinc alloy |
Adjustable Range Of Switching Point On Rising Pressure | 0.7-10 bar |
Maximum Permissible Accidental Pressure | 22.5 bar |
Possible Differential Maximum At High Setting | 7.5 bar |
Destruction Pressure | 45 bar |
Device Short Name | XMLB |
Pressure Actuator | diaphragm |
Electrical Connection | screw-clamps terminals, 1 x 0.5...2 x 2.5 mm² || 1 connector Pg 13 |
Range Of Product | Telemecanique Pressure sensors XM |
Line Rated Current | 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 || 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 || 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1 |
Pressure Switch Type Of Operation | regulation between 2 thresholds |
Cable Entry | cable gland 9-13 mm |
Product Or Component Type | electromechanical pressure sensor |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Repeat Accuracy | 2 % |
Maximum Permissible Pressure - Per Cycle | 12.5 bar |
Maximum Operating Rate | 120 cyc/mn |
[Ui] Rated Insulation Voltage | 300 V UL 508 || 500 V EN/IEC 60947-1 || 300 V CSA C22.2 No 14 |
Setting | external |
Mechanical Durability | 5000000 cycles |
Width | 35 mm |
Depth | 75 mm |
Maximum Resistance Across Terminals | 25 mOhm IEC 255-7 category 3 || 25 mOhm NF C 93-050 method A |
Possible Differential Minimum At Low Setting | 0.57 bar +/- 0.05 bar) |
Height | 113 mm |
Terminal Block Type | 4 terminals |
Short-Circuit Protection | 10 A cartridge fuse gG (gl) |
Contacts Material | silver contacts |
Possible Differential Minimum At High Setting | 0.85 bar - 0.1 bar, + 0.15 bar) |
Auxiliary Contacts Operation | snap action |
Net Weight | 0.705 kg |
[Uimp] Rated Impulse Withstand Voltage | 6 kV EN/IEC 60947-1 |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP110914EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Environment | |
Product Certifications | LROS (Lloyds register of shipping) || CCC || BV || UL || EAC || CSA |
Electrical Shock Protection Class | class I IEC 1140 || class I IEC 536 || class I NF C 20-030 |
Ambient Air Temperature For Operation | -25-70 °C |
Standards | UL 508 || CSA C22.2 No 14 || EN/IEC 60947-5-1 || CE |
Vibration Resistance | 4 gn 30-500 Hz)IEC 60068-2-6 |
Shock Resistance | 50 gn IEC 60068-2-27 |
Ip Degree Of Protection | IP66 conforming to EN/IEC 60529 |
Ambient Air Temperature For Storage | -40-70 °C |
Protective Treatment | TC standard version |
Operating Position | any position |